Date Code 20010625
Loss-of-Potential, CCVT Transient Detection,
4-7
Load-Encroachment, and Directional Element Logic
SEL-311L Instruction Manual
Again, for the maximum forward load:
[(230)
2
• (400)]/[(800) • (2000)] = 13.2
8
secondary
To provide a margin for setting ZLF, multiply by a factor of 0.9:
ZLF = 13.2
8
secondary • 0.9 = 11.90
8
secondary
For the maximum reverse load:
[(230)
2
• (400)]/[(500) • (2000)] = 21.1
8
secondary
Again, to provide a margin for setting ZLR:
ZLR = 21.1
8
secondary • 0.9 = 19.00
8
secondary
Convert Power Factors to Equivalent Load Angles
The power factor (forward load) can vary from 0.90 lag to 0.95 lead.
Setting PLAF = cos
-1
(0.90) = 26
o
Setting NLAF = cos
-1
(0.95) = -18
o
The power factor (reverse load) can vary from 0.80 lag to 0.95 lead.
Setting PLAR = 180
o
- cos
-1
(0.80) = 180
o
- 37
o
= 143
o
Setting NLAR = 180
o
+ cos
-1
(0.95) = 180
o
+ 18
o
= 198
o
Apply Load-Encroachment Logic to a Phase Time-Overcurrent
Again, from Figure 4.3:
ZLOAD = ZLOUT + ZLIN
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......