
13.51
Date Code 20060320
Instruction Manual
SEL-311C Relay
Testing and Troubleshooting
Test Procedures
Step 14. Turn on the voltage sources.
a. Apply V
A
, V
B
, and V
C
at the magnitudes and angles
listed in
b. Turn on the current test source.
c. Set the current angle to –90.0°.
d. Slowly increase the magnitude of current applied until
the Z2G element asserts, causing
OUT106
to close. This
occurs when current applied is approximately
2.49 amps.
Ground Quadrilateral Distance Element Resistive Reach Test Using Three
Voltage Sources and One Current Source
Step 1. Execute the
SHOWSET
command and verify the following
relay settings: Z1MAG, Z1ANG, E21XG, E32, XG2, RG2,
50L2, 50GZ2, k0M, k0A, T, ORDER, Z2F, and 50QF.
The example relay settings use the following settings:
Z1MAG =
7.8
Ω
Z1ANG =
83.97
°
E21XG =
3
E32 =
Y
XG2 =
9.36
Ω
RG2 =
5.00
Ω
50L2 =
0.50
50GZ2 =
0.50
k0M =
0.726
k0A =
–3.69
T =
0.00
ORDER =
Q
Z2F =
0.77
50QF =
0.5 amps secondary
Step 2. Execute the
SET
command and change the following settings.
a. Change E21MG to N, E21XG to 3, and ELOP from Y
to N. Changing the E21MG setting prevents the relay
ground mho distance elements from interfering with the
test. Changing the ELOP setting prevents the Loss-of-
Potential logic from blocking operation of the relay
distance elements if the test signals fulfill Loss-of-
Potential conditions.
Step 3. Select an output contact to indicate operation of the Z2G
element. In this example, use the
OUT106
output.
Step 4. From Access Level 2, execute the
SET L
n
command to
configure Output 6 to close for assertion of the Z2G element.
NOTE:
As you perform this test,
other protection elements can assert,
causing the relay to close other
output contacts and assert relay
targets. This is normal and is not a
cause for concern.
NOTE:
This test refers directly to the
Zone 2 ground quadrilateral distance
element, but can be applied to any
other forward-reaching ground
quadrilateral distance element zone.
To test reverse-reaching zones, simply
add 180° to the calculated test current
phase angle. Verify correct operation
of the 32GR element for the test
voltage and current signals through
use of
.
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...