Date Code 20011205
Distance, Overcurrent, Voltage,
3-29
and Synchronism Check Elements
SEL-311B Instruction Manual
Figure 3.19: Residual Ground Time-Overcurrent Element 51GT
Settings Ranges
Table 3.5: Residual Ground Time-Overcurrent Element Settings
Setting Definition
Range
51GP
pickup
OFF, 0.50–16.00 A secondary (5 A nominal phase
current inputs, IA, IB, IC)
OFF, 0.10–3.20 A secondary (1 A nominal phase
current inputs, IA, IB, IC)
51GC
curve type
U1–U5 (US curves) see Figure 9.1–Figure 9.10
C1–C5 (IEC curves)
51GTD
time dial
0.50–15.00 (US curves) see Figure 9.1–Figure 9.10
0.05–1.00 (IEC curves)
51GRS electromechanical
reset timing
Y = Enable electromechanical reset timing
N = 1 cycle reset delay
51GTC SEL
OGIC
control
equation torque
control setting
Relay Word bits referenced in Tables 9.3 and 9.4
or
set directly to logical 1—see note below.
Note
: SEL
OGIC
control equation torque control settings (e.g., 51GTC) cannot be set directly to
logical 0.
See
Section 9: Setting the Relay
for additional time-overcurrent element settings information.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......