Date Code 20011205
Distance, Overcurrent, Voltage,
3-25
and Synchronism Check Elements
SEL-311B Instruction Manual
51PT Element Settings Ranges
The 51PT phase time-overcurrent element has the following settings:
Table 3.3: Phase Time-Overcurrent Element (Maximum Phase) Settings
Setting Definition
Range
51PP
pickup
0.50–16.00 A secondary (5 A nominal phase current
inputs, IA, IB, IC)
0.10–3.20 A secondary (1 A nominal phase current
inputs, IA, IB, IC)
51PC
curve type
U1–U5 (US curves) see Figure 9.1–Figure 9.10
C1–C5 (IEC curves)
51PTD
time dial
0.50–15.00 (US curves) see Figure 9.1–Figure 9.10
0.05–1.00 (IEC curves)
51PRS electromechanical
reset timing
Y = Enable electromechanical reset timing
N = 1 cycle reset delay
51PTC SEL
OGIC
control
equation torque
control setting
Relay Word bits referenced in Tables 9.3 and 9.4
or
set directly to logical 1—see note below
Note
: SEL
OGIC
control equation torque control settings (e.g., 51PTC) cannot be set directly to
logical 0.
See
Section 9: Setting the Relay
for additional time-overcurrent element setting information.
Figure 3.18: Phase Time-Overcurrent Element 51PT
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......