I-4
M
IRRORED
B
ITS
Communications
Date Code 20011205
SEL-311B Instruction Manual
The M
IRRORED
B
ITS
protocol compatible with the Pulsar MBT-9600 modem is identical to the
standard M
IRRORED
B
ITS
protocol with the following exceptions:
The relay injects a delay (idle time) between messages. The length of the delay is one relay
processing interval. Note: An idle processing interval guarantees at least 19 idle bits at 9600
baud in an SEL-321 Relay with the system frequency at 65 Hz.
The relay resets RTS (to a negative voltage at the EIA-232 connector) for M
IRRORED
B
ITS
communications using this specification. The relay sets RTS (to a positive voltage at the
EIA-232 connector) for M
IRRORED
B
ITS
communications using the R6 or original R version of
M
IRRORED
B
ITS
.
S
ETTINGS
protocol (SEL,LMD,MBA,MBB) PROTO = MBA ?
Set PROTO = MBA to enable the M
IRRORED
B
ITS
protocol channel A on this port. Set PROTO
= MBB to enable the M
IRRORED
B
ITS
protocol channel B on this port. For the remainder of this
section, PROTO = MBA is assumed.
baud rate (300-38400) SPEED = 9600 ?
Use the SPEED setting to control the rate at which the M
IRRORED
B
ITS
messages are transmitted,
in power system cycles (~), based on the following table:
SPEED SEL-321
SEL-311B
38400
1 message per 1/8 cycle
1 message per 1/4 cycle
19200
1 message per 1/8 cycle
1 message per 1/4 cycle
9600
1 message per 1/4 cycle
1 message per 1/4 cycle
4800
1 message per 1/2 cycle
1 message per 1/2 cycle
enable hardware handshaking (Y,N,MBT) RTSCTS= N ?
Use the MBT option if you are using a Pulsar MBT 9600 baud modem. With this option set, the
relay will transmit a message every 1/2-power system cycle and the relay will deassert the RTS
signal on the EIA-232 connector. Also, the relay will monitor the CTS signal on the EIA-232
connector, which the modem will deassert if the channel has too many errors. The modem uses
the relay’s RTS signal to determine whether the new or old M
IRRORED
B
ITS
protocol is in use.
Mirrored Bits Receive bad pickup (1-10000 sec) RBADPU= 60 ?
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......