Date Code 20011205
Application Settings for SEL-221 Series Relays
14-33
SEL-311B Instruction Manual
SEL-221C
TO
SEL-311B S
ETTINGS
C
ONVERSION
G
UIDE
Set APP = 221C in the SEL-311B to configure the relay to closely approximate the features,
performance, and settings of an SEL-221C. When APP = 221C, the SEL-311B:
1. Configures itself as a phase distance and phase and ground directional overcurrent relay
with voltage supervised reclosing.
2. Configures contact inputs and contact outputs to emulate those in an SEL-221C.
3. Presents the user only with those settings associated with SEL-221C type features.
4. Automatically calculates all other settings required to simulate an SEL-221C.
If additional capability is needed (e.g., M
IRRORED
B
ITS
or SEL
OGIC
control equations) the relay
may be returned to the setting APP = 311B to make all of the SEL-311B settings visible. It is
important to remember that changing from APP = 311B to APP = 221C changes settings in the
SEL-311B. Changing from APP = 221C to APP = 311B makes more SEL-311B settings visible,
but does not change any other settings. If SEL-311B functions are used after setting APP is
changed from 221C to 311B, do not change setting APP back to 221C.
As described above, when setting APP = 221C, the user is presented only with SEL-311B
settings associated with the features found in an SEL-221C. This section explains how to make
those remaining SEL-311B settings directly from the settings used in an SEL-221C.
There are mainly two kinds of settings in the SEL-311B, relay settings and SEL
OGIC
settings.
Relay settings are settings for protective elements. SEL
OGIC
settings are Boolean expressions
used to customize the logic of the SEL-311B. To set the SEL-311B to emulate an SEL-221C,
follow these four steps:
1. Turn on the SEL-221C application setting by making setting APP = 221C. See
Application Settings
below.
2. Convert the appropriate SEL-221C settings to SEL-311B settings using the simple
equations shown in Table 14.12. Be sure to convert from primary quantities (SEL-221C
settings) to secondary quantities (SEL-311B settings). See
Convert SEL-221C Primary
Quantities to SEL-311B Secondary Quantities
below.
3. For each Mask Logic setting in the SEL-221C shown in Table 14.13, create an
equivalent SEL
OGIC
control equation using the logical OR of each bit asserted in the
mask, as shown in Table 14.14.
4. Test the relay to verify intended performance.
The remainder of this section shows how to perform steps 1 through 3 above, and also gives an
example of step 3.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......