Date Code 20011205
Testing and Troubleshooting
13-47
SEL-311B Instruction Manual
Relay Does Not Respond to Faults
1. Verify that the relay is properly set.
2. Verify that the test source is properly set.
3. Verify that the test connections are correct.
4. Ensure that the analog input cable between transformer secondary and main board is not
loose or defective.
5. Inspect the relay self-test status with the
STA
command or with the front-panel STATUS
button.
R
ELAY
C
ALIBRATION
The SEL-311B Relay is factory-calibrated. If you suspect that the relay is out of calibration,
please contact the factory.
F
ACTORY
A
SSISTANCE
We appreciate your interest in SEL products and services. If you have questions or comments,
please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA USA 99163-5603
Tel: (509) 332-1890
Fax: (509) 332-7990
Internet: www.selinc.com
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......