3-12
Distance and Overcurrent Elements
Date Code 20011205
SEL-311A Instruction Manual
M311A049
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
Fault Location in Percent of Set Reach
O
pera
tin
g
Time
in
Cycles
SEL-311A Mho Ground Operating Times
Single-Line-to-Ground Faults
SIR = 0.1
SIR = 1.0
SIR = 10.0
SIR = 30.0
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
Fault Location in Percent of Set Reach
Tri
p
Time
in
Cycles
SEL-311A Phase Mho Operating Times
Phase-to-Phase Faults
SIR = 0.1
SIR = 1.0
SIR = 10.0
SIR = 30.0
Figure 3.8: Ground and Phase Distance Speed Curves
Additional Distance Element Supervision
The SEL-311A uses Relay Word bit VPOLV for positive-sequence memory supervision of mho
characteristics. VPOLV asserts when the memorized positive-sequence polarizing voltage is
greater than 1 Volt.
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......