Table 2.4: Relay Word Bit Summary
Z1P
Zone 1 phase fault, instantaneous output (set by Z1%)
Z1G
Zone 1 ground fault, instantaneous output (set by Z1%)
Z2PT
Zone 2 phase fault, time delayed (set by Z2% and Z2DP)
Z2GT
Zone 2 ground fault, time delayed (set by Z2% and Z2DG)
Z3
Zone 3 phase or ground fault, instantaneous output (set by Z3%)
Z3T
Zone 3 phase or ground fault, time delayed (set by Z3% and Z3D)
3P21
Three-phase fault condition detected by phase distance relays
32Q
Negative-sequence directional element
67N
Residual instantaneous overcurrent (set by 67NP and 67NTC)
51NP
Pickup of residual time-O/C (set by 51NP and 51NTC)
51NT
Timeout of residual time-overcurrent element
50NG
Sensitive residual or phase overcurrent condition (set by 50NG)
50P
Phase overcurrent condition (set by 50P)
50H
High-set phase overcurrent condition (set by 50H)
IN1
Logic Input 1 (use for direct trip, reclose initiate/cancel, etc.)
REJO
Remote-end-just-opened condition
LOP
Loss-of-potential condition
52BT
Inverted 52A input, delayed by 52BT setting at pickup and dropout
27S
Synchronizing undervoltage condition (Tests VS against VLO setting)
27P
Polarizing undervoltage condition (Tests VP1* against VLO setting)
59S
Synchronizing overvoltage condition (Tests VS against VHI setting)
59P
Polarizing overvoltage condition (Tests VP1* against VHI setting)
SSC
Synchronization-supervised condition (set by 25DV, 25T, SYNCP)
VSC
Voltage-supervised condition (set by PSVC for disable/LSDP/LPDS/either)
*VP1 = Positive-sequence voltage applied to the polarizing voltage inputs.
The use of the Relay Word and programmable masks provides the user great flexibility in
applying the SEL-221F relay without the need for rewiring panels or changing jumpers on
circuit boards.
Remote-End-Just-Opened (REJO) Logic
Remote-end-just-opened detection logic can speed up clearing of internal faults, beyond the
reach of Zone 1. A three-phase current condition (e.g., load) must first be established, as
detected by the 3G50 or 3P50 logic condition. If, during a short time period after its
disappearance (signifying the other end tripped), current still remains in at least one phase
(signifying that the fault is still present), then the
REJO
(remote-end-just opened) bit is
asserted.
Date Code 920508
Specifications
SEL-221F, -1 Instruction Manuel
2-21
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...