background image

 
 

ThermoControl Plus M2

 

 

 

2-stage or modulating controller 

with two control zones 

(alternative: four control zones 1-stage) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Operating and  

Installation Manual

 

 
 
 

 
 
 

 

Schwank GmbH - Bremerhavener Str. 43 - 50735 Cologne - Germany 

 

Tel: +49 (0)221- 7176-0  Fax: +49 (0)221-7176-288

 

 

E-mail: [email protected] 

  

Internet: www.schwank.de 

Subject to technical changes. Version 09/10 

Содержание ThermoControl Plus M2

Страница 1: ...rol zones alternative four control zones 1 stage Operating and Installation Manual Schwank GmbH Bremerhavener Str 43 50735 Cologne Germany Tel 49 0 221 7176 0 Fax 49 0 221 7176 288 E mail info schwank de Internet www schwank de Subject to technical changes Version 09 10 ...

Страница 2: ...4 4 4 How to protect the time program 12 4 4 5 How to program the switching points 13 4 5 Holiday program 14 4 6 Manual operation FIX 15 4 7 Button for chimney sweep mode 15 5 SET UP THE OPERATING PARAMETERS 16 5 1 Enter the number of control zones 16 5 2 Set up the parameters in the display 17 5 3 The warm up time optimiser 18 5 4 COPY 19 5 5 How to do a security save and how to reload all parame...

Страница 3: ...odulating control for gas infrared heaters Override day temperature mode h Available as a special feature is the extension of the programmed heating period by a manually operated button This button can be installed parallel to the sensor By pushing the button 1 sec the nominal value of the programmed temperature in the selected control circuit is maintained for an additional programmable time peri...

Страница 4: ...line has to be protected by a fuse with max 16 A on the part of the builder Please install the ThermoControl Plus M2 ensuring conformity to the wiring diagram which is located in the switchboard Ensure that the controller and consumer are connected by a 1 5 mm2 cable further on controller and sensor have to be connected by a telephone cable Install the room temperature sensor between the radiation...

Страница 5: ...f every parameter shown in the display The chosen selected parameter can be modified by the buttons 7 Clock button Can be used to display and modify time and date 8 FIX To change between programmed and FIX modes and back 9 PR To check and modify the weekly time program in the displayed control circuit 10 CLR Clear button To delete a switch point or a complete time program 11 Copy This button can b...

Страница 6: ...onal Recording device of the chosen control circuit This number informs which relay output and which sensor inputs are used in the specific control circuit Display of the outside temperature only in case of an outdoor temperature sensor ATF The main base display gives all important operating data further information can be received by pushing the DISP button Value of the entered anti freezing temp...

Страница 7: ...chosen by pushing the ZONE button Now all settings of the control zones can be managed and progressed During the optimised warm up time you will notice the OPT symbol The activation time of a specific zone is accelerated in dependency of the preheating performance compared to the entered heating time This function can be deactivated only in the setup menu An outside sensor ATF is necessary While u...

Страница 8: ... DISP button automatically after one minute without pushing a button the current display switches back to the main display The current day or night temperatures can be displayed if you push or button The displayed values can be modified by pushing All modifications are saved immediately The temperatures can be changed on a scale of 3 up to 35 C ...

Страница 9: ...ds for the third day in the ongoing week in other words Wednesday 1 Monday etc After using the button once more the display switches back to the normal clock The display ends at the base display if you press the DISP button Setting the time To change the time the SEL button has to be pressed At first the minutes start to blink 03 which can be modified by using After pushing the SEL button again th...

Страница 10: ...spectively will be shown on the display When the year has been modified the day of the week might be changing according to the calendar in this case 3 To change the setting you have to press SEL At first the month 5 will start to blink the setting can be modified with To change the day please push the SEL button again Now the day starts to blink 21 The day can also be modified with the buttons Onc...

Страница 11: ...hanges to the first switching point In this case the display shows At 6 00 o clock in the morning on every day of the week 1 2 3 4 5 6 7 Day the controller is instructed to change to day temperature The small number on the display 1 is the program number of the switching point To read off the second switching point of time 2 you have to press the PR button In the picture 9 00 o clock in the evenin...

Страница 12: ...tching points are independent of the battery charge because the program is saved on a secured EEPRON memory card Thus time programs cannot get lost as a consequence of a battery change or in the case of any other mistake If you want to clear a switching point you have to push and hold the CLR button The symbol CLR will blink in the display so that you are warned you are going to clear a switching ...

Страница 13: ...oups or only single days 1 Monday Afterwards you can modify the hour by pushing the SEL button 12 The requested time 7 can be achieved with After that you select the minutes with SEL 00 The requested time 35 can be adjusted with Finally the PR button has to be pushed The SET symbol starts to blink shortly while the data is being saved Afterwards the display switches to the next free switching poin...

Страница 14: ...rol circuits which are working in the automatic mode If a control circuit is working on a fixed mode FIX the holiday program has no effect on this function If you push the button again the start of the holiday period can be modified A by pressing you can set up year month and day The holiday program starts off at 0 00 o clock on the desired date After you have modified the start A you will have to...

Страница 15: ...peration mode appears for example continuous FIX mode The control unit switches back to the main display and the selected mode is activated night temperature mode day temperature mode anti freezing temperature By pushing the button the heater runs with full power independent of the current room temperature You can switch back to the base display mode by pushing this button again Push FIX to get ba...

Страница 16: ... P2 P3 all parameters switch back to the factory setting chapter 5 1 und 5 2 P0 4 Control zones gas fired air heater P1 4 Control zones single stage P2 1 Control zone two stage or modulating control 2 control zones single stage P3 2 Control zones two stage or modulation Control mode can be selected by a small separate jumper Upper position modulating control mode Lower position two stage control m...

Страница 17: ...t an optimal place the measured temperature can be revised 9 9 9 9 C t1 After starting the heater it runs with full power until it stops at the programmed time in this case 0 5 minute t2 For the displayed time the heater stops completely 5 60 Sec it only appears if the t1 doesn t equal zero Min turn on time of the heater 0 15 min Ability of a restart t3 The heater starts off with full load for 1 m...

Страница 18: ...ter the heating circuits have been switched off the extract fan continues until the programmed time is achieved From 0 up to 60 minutes can be programmed it appears only in the AUt ventilation mode The optimised warm up time can be switched on AUt or off OFF The effective warm up time is shown Automatic switch from summer over to wintertime 1h This function can be activated AUt and deactivated OFF...

Страница 19: ... Push COPY to paste the data of ZONE 2 into ZONE 3 The numeric 2 and 3 are signalling the completion of the copy process Now push the SEL button to select a new zone In the next step ZONE 4 is selected 4 starts to blink Push the COPY button to paste the data into ZONE 4 The display is signalling the completion of the copy process The data of ZONE 1 has now been pasted into ZONE 2 3 4 To finish the...

Страница 20: ... possible to reload the factory settings Protected function Press CLR and simultaneously The SAVE symbol will appear in the display Now push DISP the display will start to blink the parameters are saved afterwards the display switches back to the main menu If you press CLR and SEL simultaneously the LOAd symbol appears in the display Then press the DISP button and the parameters that were saved by...

Страница 21: ...tention that live L and neutral N wires are connected correctly in accordance with the wiring schemes of the selected application program 6 2 Sensor connections The sensor has to be connected with two wires There is no need to provide the sensor with shielded cables because the controller includes an effective protector The length of the wires up to 200 m has no influence on the accuracy of the me...

Страница 22: ... common flue fan of control circuit heating zone 1 and 2 In case that one or both heating zone outputs are activated the flue fan control will be activated as well If both heating zone outputs switch off the flue fan also switches off immediately or delayed after a programmable period of time chapter 5 2 In case that single stage operated heaters are divided into two heating zones and one zone is ...

Страница 23: ...eature contact input fault can be selected in the SETUP menu 5 2 The external error message can be connected to inputs 72 73 In case of an error message option the signal ERR and RES as well as ERROR begins to blink At the same time the Error relay switches on The operation mode of the controller is not changed due to the error signal If the remote contact is activated it is not possible to change...

Страница 24: ... Battery low or discharged The battery has to be changed immediately The battery is located at the inside of the control unit Type 1 5V AA Use long term batteries Before changing the batteries please read the general security instructions Alarm signal Does not point out the kind of operational error It only shows that an error message has arrived at the alarm contact The controller switches off al...

Страница 25: ...wo stage only 0 5 3 0 C Integration band modulating only 1 5 9 9 C Integration time two stage or modulating operation only 10 99 minutes Sensor correction 9 9 9 9 C Flue fan delay time 0 60 minutes Clock calendar Real time clock with calendar Clock power 1 5 V AA battery durability 3 years automatic summer winter time correction 1 hour can be deactivated correction to summer time last Sunday in Ma...

Страница 26: ... 26 8 Appendix Wiring diagram ThermoControl Plus M 1 2 4 1 8 zones single stage luminous heater ...

Страница 27: ... 27 Wiring diagram ThermoControl Plus M 1 2 4 1 4 zones two stage luminous heater ...

Страница 28: ... 28 Wiring diagram ThermoControl Plus M 1 2 4 1 4 zones modulating luminous heater ...

Страница 29: ... 29 Wiring diagram ThermoControl Plus M 1 2 4 1 8 zones single stage tube heater ...

Страница 30: ... 30 Wiring diagram ThermoControl Plus M 1 2 4 1 4 zones two stage tube heater ...

Страница 31: ... 31 Wiring diagram ThermoControl Plus M 1 2 4 1 4 zones modulating tube heater ...

Страница 32: ... 32 Wiring diagram ThermoControl Plus M 1 2 4 1 4 zones warm air heater aeroSchwank AR and AT ...

Страница 33: ... 33 Wiring diagram warm air heater AR and AT ...

Страница 34: ...7638 14 7271 15 6904 16 6622 17 6339 18 6057 19 5775 20 5492 21 5273 22 5055 23 4836 24 4617 25 4398 26 4227 27 4057 28 3886 29 3715 30 3545 Temperature Sensor Characteristic Line ThermoControl Plus 0 2000 4000 6000 8000 10000 12000 14000 16000 0 2 4 6 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 Temperature C Ohmic Resistance in Ohm ...

Отзывы: