Schwank primoSchwank Скачать руководство пользователя страница 1

supra/primo Manual 

IM091112 

RD: NOV 2009 

RL: 11A - BA 

  

 

HIGH EFFICIENCY COMBINED INTENSITY 

Gas-Fired Luminous (High Intensity) Infrared Heaters 

INSTALLATION / OWNER’S MANUAL 

Improper installation, adjustment, alteration, service or 
maintenance can cause property damage, injury or death.   

Read the installation and operating and maintenance instruc-
tions thoroughly before installing or servicing this equipment. 

Not approved for use in any residential application. 

 

SAFETY ALERT

This heater must be installed and serviced only  by a trained gas service techni-
cian. Failure to comply could result in personal injury, death, fire and/or property 
damage. 
Do not store or use gasoline or other flammable vapours and liquids in the 
vicinity of this or any other gas fired appliance. 

 

IF YOU SMELL GAS



Extinguish any open flame 



Do not attempt to light this or any other appliance 



Don’t touch any electrical switch, or telephone 



Immediately leave the area and call your gas supplier from a neighbor’s 
phone  



Follow any and all instruction from your gas supplier 



If your gas supplier is not available, call the fire department 

WARNING 

FIELD CONVERTIBILITY:

   

This appliance is field con-
vertible to LP gas. Use kit 
available from manufacturer. 
See Page 14.   Follow all 
local and national codes. 

INSTALLER: PRESENT THIS MANUAL 

TO THE END USER.  

Keep this manual in a secure place .  
   Record for future reference

Model #:  

Serial #:  

                

(located on heater rating label)

 

primoSchwank

 & 

supraSchwank 

Содержание primoSchwank

Страница 1: ...roperty damage Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other gas fired appliance IF YOU SMELL GAS Extinguish any open flame Do not attempt to...

Страница 2: ...reof may not be reproduced in any form without prior written consent from The Manufacturer Unauthorized use or distribution of this publication is strictly prohibited Schwank Group Schwank and InfraSa...

Страница 3: ...IPING 14 GAS CONVERSION 14 TOPIC PAGE 10 ELECTRICAL THERMOSTAT 15 11 INSTALLATION 16 DIMENSIONS CAPACITIES 17 12 LIGHTING INSTRUCTIONS 19 13 SHUT DOWN INSTRUCTIONS 19 14 DISCOLORATION OF HEATER BODY 1...

Страница 4: ...dures In case of discrepancy the latest codes standards and installation manual will take pri ority over prior releases IMPORTANT DO NOT INSTALL THIS HEATER IN A STRUCTURE WITH NO INSULATION IN THE RO...

Страница 5: ...ied to connect to the gas supply to the heater in accordance with all local state provincial and national codes ANSI Z223 1 NFPA 54 in USA B149 1 in Canada and as indicated in this manual WARNING WARN...

Страница 6: ...clearances from the heater to the combustibles For your convenience a sign is supplied with this heater see page 8 for de tails Such signs must either be posted adjacent to the heater thermostats or...

Страница 7: ...GN IS SUPPLIED USE AN INDELIBLE MARKER TO ENTER VALUES H S F B ON POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A PROMINENT LOCATION See next page for details C A A S S SUSPENDED HORIZONTALLY...

Страница 8: ...to Table 1 to get the value C clearance to combustibles below heater that corresponds to the model you are installing Subtract the clearance below the heater C from T to get value H maximum material s...

Страница 9: ...mer cial industrial non residential indoor spaces IMPORTANT DO NOT INSTALL THIS HEATER IN A STRUCTURE THAT HAS NO INSULA TION IN THE ROOF CONDENSATION WILL OCCUR This heaters cannot be installed insid...

Страница 10: ...ARNING 5 PRE INSTALLATION SURVEY It is recommended that a full heating design including heat loss calculation be conducted on the structure or area to be heated Heater sizing and placement must consid...

Страница 11: ...ow sufficient com bustion air supply to the heater 6A SERVICE CLEARANCE To allow servicing of burner and controls provide a minimum clearance of 24 inches 61 cm from the gas supply ignition controls o...

Страница 12: ...al ues air movement change and other site conditions If in doubt please contact Schwank Technical Services For spot heating the distance above the floor can be reduced by 2 to 4 feet 61 to 132 cm depe...

Страница 13: ...e Maximum zone size is limited by the total input that can be handled by the capacity of an exhauster and by the proximity of the exhauster to heaters in the zone Exhauster Location Proximity Exhaust...

Страница 14: ...ATCH OR OPEN FLAME OF ANY KIND TO TEST FOR LEAKS NEVER OPERATE THE HEATER WITH LEAKING CONNECTIONS Leak test according to local or national codes DO NOT use pressure greater than 1 2 psig to pressure...

Страница 15: ...ter requires 24 Volt 60 Hz electrical transformer sized at 40 VA Multiple heaters in a zone are powered by a single transformer The proper transformer is 24 Volt AC 60 Hz sized at 40 VA for the first...

Страница 16: ...on when angle mounted The heater requires an Angle Mounting Bracket JO 0331 XX available as an op tional accessory for angle mounting over 30 up to 45 the Angle Mounting Bracket bolts to the suspensio...

Страница 17: ...3 1 76 500 22 4 69 730 20 4 A In cm 23 75 60 3 34 50 87 6 45 62 116 67 32 171 S In cm 21 7 55 1 32 6 82 8 43 5 110 5 65 165 WEIGHT Lbs kg 23 5 10 7 33 6 15 2 40 3 18 3 54 9 24 9 supraSchwank MODEL CAP...

Страница 18: ...supra primo Manual IM091112 RD NOV 2009 RL 11B BA 18 FIGURE 5 TYPICAL SUSPENSION HARDWARE supplied by others FIGURE 6 MOUNTING HEATER...

Страница 19: ...occur on the heater body where the products of combustion discharge from the heater This discoloration is due the deposit of ambient air borne particulate or gases that have passed through combus tio...

Страница 20: ...supra primo Manual IM091112 RD NOV 2009 RL 11B BA 20 15 ELECTRICAL WIRING DIAGRAM 24V CONTROL...

Страница 21: ...supra primo Manual IM091112 RD NOV 2009 RL 11A BA 21 16 ELECTRICAL WIRING DIAGRAM LINE VOLTAGE 120V CONTROL...

Страница 22: ...no particulate matter is fouling the seating of the valve and allowing gas leakage replace valve if necessary Improper installation adjustment alteration service or maintenance can cause property dama...

Страница 23: ...ION FROM THERMOSTAT TO FAN MOTOR CHECK THERMOSTAT REPLACE IF NECESSARY NO IS FAN MOTOR OPERATING CHECK EXHAUST FAN MOTOR REPLACE IF NECESSARY NO IS THERE VOLTAGE TO THE TRANSFORMER YES CHECK ELECTRICA...

Страница 24: ...VOLTAGE WIRE C O N N E C T I O N FROM SPARK IGNITER TO IGNITION MODULE ENSURE HIGH VOLTAGE S P A R K S A R E GENERATED ON THE IGNITION CONTROL TERMINAL BY FOLLOWING THE STEPS AS SHOWN BELOW SHUT OFF...

Страница 25: ...THE SENSING WIRE IS SECURELY CONNECTED TO THE SENSING PROBE CLEAN THE SENSING PROBE ON THE SPARK IGNITER ENSURE THE FLAME SENSOR IS WITHIN 1 4 ABOVE THE CERAMIC TILE CHECK FLAME SIGNAL WITH METER IF...

Страница 26: ...1296 MM primoSchwank 15 LPG 2 10 mm JO 0313 LP 2 06 mm JO 1206 MM 2 04 mm JO 1204 MM 2 01 mm JO 1201 MM DO NOT INSTALL primoSchwank 20 NG 3 75 mm JO 0311 NG 3 68 mm JO 1368 MM 3 64 mm JO 1364 MM 3 59...

Страница 27: ...S87C DSI CONTROL 1 On a call for heat the S87C DSI Control will check for a false flame condition short to ground The module will lock out if a false flame condition is present Reset is usually done f...

Страница 28: ...ECHNICIAN MUST COMMISSION THE APPLIANCE AND COMPLETE THE COMMISSIONING REPORT CONFIRM THAT THE APPLIANCE IS INSTALLED ACCORDING TO ALL LOCAL AND NA TIONAL CODES AND THE INSTRUCTIONS IN THIS MANUAL ENS...

Страница 29: ...LINE ADEQUATELY SIZED FOR SYSTEM VOLUME YES NO HAVE GAS LINES AND BRANCHES BEEN PURGED OF AIR YES NO THIS HEATER WAS FIELD TEST FIRED WITHOUT ANY MALFUNCTION YES NO INLET GAS SUPPLY PRESSURE WITH HEA...

Страница 30: ...control of IR systems Automatic unoccupied setback of 9 F 5 C can be overridden Low Voltage Digital Thermostat 24 Volts FOR SECURITY TO PREVENT UNAUTHORIZED OPENING 2 Stainless Steel Tamper Proof Scre...

Страница 31: ...ble Gas connector 1 2 x 24 Pressure Equalizer Venturi Cover For drafty locations near overhead doors etc Control Center Transformer Relay AT72D 40VA Transformer for single heater Transformer Size Heat...

Страница 32: ...1112 RD NOV 2009 RL 11B BA 32 24 PARTS LIST 6 1 2a 2 16a 16 16b 17a 17 16b 12 11 7 4 3 5 15 8 9 13 PRIMO Heater body not insulated SUPRA Insulated body with aluminized steel cover Reverberating Screen...

Страница 33: ...2 18mm SUPRA ONLY JU 0320 NG SUPRA 20 NG 3 35mm SUPRA ONLY JU 0321 LP SUPRA 30 LP 2 60mm SUPRA ONLY JU 0321 NG SUPRA 30 NG 4 05mm SUPRA ONLY 4 ORIFICE HOLDER JO 0307 XX PRIMO SUPRA 10 JO 0307 AA PRIMO...

Страница 34: ...201 DD FENWAL 2462D901 029 DOUBLE IGNITION CONTROL PRIMO SUPRA 40 JX 0202 PX HONEYWELL S87C DS1140 SYNETEK CONTROL REPLACEMENT KIT 13 HIGH VOLTAGE SPARK WIRE JO 0323 XX STANDARD JO 0329 SP PROCESS NOT...

Страница 35: ...y caused by any contingency beyond its control including war government restrictions or restraints strikes fire flood acts of God or short or reduced supply of raw materials or products WARRANTY PROCE...

Отзывы: