SEM(U) / IT(U) Manual 

RD: Sept, 2005 

RL: 03B 

KH 

 

FIELD CONVERTIBILITY: 

 
“The conversion shall be carried out in accordance 
with the requirements of the provincial authorities 
having jurisdiction and in accordance with the 
requirements of the B149.1 (latest edition) 
INSTALLATION CODE” in Canada, and the ANSI 
Z223.1 (latest edition) in the U.S.A. 

SERIES 

 

LOW INTENSITY TUBE TYPE 

INFRA RED HEATERS 

 

FOR YOUR SAFETY: 

 
Do not store or use gasoline or other flammable va-
pours and liquids in the vicinity of this or any other 
appliance.

 

If you smell Gas: 
>Extinguish any open flames 
>Don’t touch electrical switches 
>Call your Gas supplier immediately  

INSTALLATION / OWNER’S MANUAL  

SEM(U)    

 

IT(U)

 

 

Содержание IT 110-30

Страница 1: ...s of the B149 1 latest edition INSTALLATION CODE in Canada and the ANSI Z223 1 latest edition in the U S A SERIES LOW INTENSITY TUBE TYPE INFRA RED HEATERS FOR YOUR SAFETY Do not store or use gasoline...

Страница 2: ...http www schwankheaters com InfraSave Inc Mississauga Ontario Waynesboro Georgia Phone 1 866 INFRASV 463 7278 Fax 1 866 724 9265 http www infrasave com e mail info infrasave com NOTICE The Manufactur...

Страница 3: ...NCORPORATING 90 DEGREE ELBOWS 7 8 SUSPENSION SYSTEM 8 9 BURNER AND TUBE INSTALLATION 10 10 REFLECTOR INSTALLATION 11 TOPIC PAGE NUMBER 11 FLUE VENTING 14 12 COMBUSTION AIR DUCT 16 13 GAS SUPPLY INSTAL...

Страница 4: ...GP MSEM BX 03B SEM U IT U Manual RD Sept 2005 RL 03B KH...

Страница 5: ...OTHER THAN SPACE HEATING Use for process applications will void the C S A certification and may require field inspection and or certification such as offices and shops which commu nicate with areas f...

Страница 6: ...0 0 10 239 SEMU ITU 200 30 31 11 10 287 SEM IT 175 70 69 4 175 000 10 240 SEM IT 175 60 59 8 10 283 SEM IT 175 50 50 0 10 239 SEMU ITU 175 30 31 11 10 287 SEM IT 155 60 59 8 155 000 Not Required 283 S...

Страница 7: ...Kit TM 1010 SX can also be used as a 10 ft extension kit the installer will need to remove the turbulator refer to Turbulator Chart in the I O Manual Stand Alone Kits Primary Kits Secondary Kits 200 0...

Страница 8: ...nstruction and equipment to provide a minimum clear ance of 24 inches from the end of burner housing for servicing and cleaning of burner blower and controls A minimum horizontal clearance of 4 ft fro...

Страница 9: ...1 17 34 TABLE 3 MINIMUM CLEARANCES TO COMBUSTIBLES MODEL SUSPENDED HORIZONTALLY SUSPENDED AT AN ANGLE UP TO 45 DEGREES TOP SIDE BELOW TOP REAR FRONT BELOW A B C D E F G SEM IT 200 7 22 68 7 1 57 68 S...

Страница 10: ...ocked with heater E Combustion air intake from outside through wall F Combustion air intake from outside through roof G Combustion air intake from inside building IMPORTANT STRAIGHT TUBE MODEL ONLY B...

Страница 11: ...evices such as rods are used in place of chain swing joints or other means of sufficient length must be provided to compensate for expansion FIGURE 4 SEM TYPICAL HANGER SUPPORT SPACING FIGURE 3 SUGGES...

Страница 12: ...tabilize burner 1 2 3 4 ALL TUBES MUST BE SUSPENDED BY TWO 2 HANGERS PER 10 LENGTH MOUNTED APPROXIMATELY 6 TO 12 IN FROM EACH TUBE END 10 13 2 11 4 3 5 6 8 7 9 1 1 12 3 4 ALL TUBES MUST BE SUSPENDED B...

Страница 13: ...the first sec tion with a welded Flange the second section is aluminized and subsequent lengths are steel painted Slacken the bolts and slip the coupler over the end of the pipe to be joined making su...

Страница 14: ...result in overheating of controls and combustible materials Use only non combustible mounting hardware Side reflectors can be added to the heaters as an option They should be secured directly to the...

Страница 15: ...SEM IT 110 30 14 SEMU ITU 110 20 10 SEMU ITU 110 15 14 SEM IT 80 40 10 SEM IT 80 30 14 SEM IT 80 20 14 SEMU ITU 80 15 14 SEMU ITU 80 10 14 SEM IT 60 30 14 SEM IT 60 20 14 SEMU ITU 60 10 14 NOTE Where...

Страница 16: ...GP MSEM BX 03B SEM U IT U Manual RD Sept 2005 RL 03B KH FIGURE 16 REFLECTOR EXTENSIONS JS 0509 XX P OPTIONAL IF REQUIRED Using S Hooks attach the two Reflectors Make sure S Hooks are closed 10 Page 12...

Страница 17: ...except that portion of vent passing through a combustible wall or roof then type B vent may be used as per CSA s interim requirement When venting horizontally the flue vent system must slope downward...

Страница 18: ...nt nor the combustion air duct is to exceed 50 ft in length Exceeding the allowable lengths may create condensation problems and will void CSA Design Certification The horizontal flue vent shall not t...

Страница 19: ...reduced by ten feet for every 90o vent elbow installed Where the vent pipe passes through areas where the ambient temperature is likely to produce condensation of the flue gases the vent pipe shall be...

Страница 20: ...er during any pressure testing of the gas supply piping system If a rigid gas pipe connection is made then compensation for normal gas supply pipe expansion and radiant tube expansion must be provided...

Страница 21: ...f water column pressure for propane gas The supply line gas pressure must be checked with all the heater s op erating Installation of a gas line trap drip leg is required at the inlet connection tee f...

Страница 22: ...w for 1 expansion for every 10 length of tube In order to address this characteristic it is suggested that the gas line flue vent and combustion air intake if used be installed in such a manner that n...

Страница 23: ...e black wire MUST be wired to Hot and the white wire MUST be wired to Neutral If the polarity is reversed the module will not function correctly and will eventually burn out 16 HIGH ALTITUDE INSTALLAT...

Страница 24: ...ce before another ignition attempt After inter purge the control will attempt two additional igni tion trials If these attempts are unsuccessful the control will go into lockout mode Flame Failure of...

Страница 25: ...eps 19 RECOMMENDED MAINTENANCE THE TUBE HEATER BURNER IS COMPLETELY FACTORY ASSEMBLED AND TESTED ANY ALTERATION VOIDS THE CSA CERTIFICATION AND MANUFACTUR ERS WARRANTY FOR ADDITIONAL INFORMATION CONTA...

Страница 26: ...GP MSEM BX 03B SEM U IT U Manual RD Sept 2005 RL 03B KH 20 CA SERIES WIRING DIAGRAM 12OV THERMOSTAT Page 22...

Страница 27: ...H IS CLOSING WHEN BLOWER IS RUNNING REPLACE DEFECTIVE SWITCHES SPARK ACROSS IGNITER OR IGNITER SENSOR GAP NO SEE SPARK IGNITION CIRCUIT on Page 24 PULL IGNITION LEAD AND CHECK SPARK CHECK SPARK GAP AD...

Страница 28: ...URNER FLAME COVERS ELECTRODE IF CHECKS ARE OKAY REPLACE IGNITION CONTROL NOTE IF IGNITION CONTROL GOES INTO LOCKOUT MODE RESET THE SYSTEM NOTE IF GROUND IS POOR OR ERRATIC SHUTDOWNS MAY OCCUR OCCASION...

Страница 29: ...e the ignition control goes into safety lockout and interrupts the spark circuit Touch one end of the jumper firmly to the ignition control GND terminal DO NOT remove the existing ground lead Slowly m...

Страница 30: ...BY THE LICENSED GAS INSTALLER ALLEVIATE NUISANCE CALL BACKS FOR THE CONTRACTOR THE FOLLOWING A CONTRACTOR IS CALLING FOR TECHNICAL SUPPORT MUST PROVIDE THE FOLLOWING INFORMATION FROM HIS COMPLETED CO...

Страница 31: ...WHAT IS THE LINE VOLTAGE READING AT THE HEATER VOLTS WHAT IS THE VOLTAGE READING AT THE IGNITION MODULE VOLTS WHAT IS THE FLAME SIGNAL STRENGTH IN uA FROM SENSOR uA microamps IS HEATER CONTROLLED BY A...

Страница 32: ...OR SEM IT SERIES TUBE HEATERS Flue Vent Terminals 4 wall horizontal 6 wall horizontal Flue Vent Terminals 4 roof vertical 6 roof vertical JA 0528 XX JA 0529 XX JA 0530 XX JA 0531 XX JA 0516 SW JA 0514...

Страница 33: ...plate hangers JS 0508 SM JS 0513 SM JL 0772 XX TM 1010 SX JS 0509 XX P Line Voltage Thermostat 10 Tube Reflector Extension Kit 1 10 Steel Tube l l0 Reflector 2 Wire Hangers 1 Coupler 180 degree Alumi...

Страница 34: ...ept 2005 RL 03B KH TruTemp Thermostat Do Not use in wet or corrosive environments JM 0150 XX JS 0569 XX JM 0303 KT JS 0532 SE Low Voltage Thermostat 24 Volts Transformer Relay for 1 to 7 heaters per z...

Страница 35: ...EM U IT U Manual RD Sept 2005 RL 03B KH Hanging Chain box of 50 ft JL 0798 XX JA 0587 XX JA 0780 XX JS 0532 VC Touch Up Paint High Temp 369g aerosol can Tube Protection Screen 5 feet long Fresh Air In...

Страница 36: ...S 0733 DM JS 0734 DM JS 0735 DM JS 0736 DM SEM IT 130N JS 0758 MM JS 0757 MM JS 0756 MM JS 0755 MM JS 0703 DM JS 0704 DM JS 0705 DM JS 0720 IN SEM IT 130L JS 0729 DM JS 0729 DM JS 0730 DM JS 0730 DM J...

Страница 37: ...ents or parts All labor or service charges shall be paid by the owner This warranty does not cover heating products improperly installed misused exposed to or damaged by neg ligence accident corrosive...