26
STS
-
JZ
-
F / IQ
-
F I&O Manual Z83.20
-
2016
IM101220
RD: APR 2019
RL: 20C
16.
SUSPENDING THE SYSTEM
-
GENERAL
Inadequate or improper suspension of the tube heater can result in collapse of
the system, property damage, and personal injury or death.
It is the installer
’
s responsibility to ensure that the hardware and structural sup-
ports from which the heater is suspended are sound and of adequate strength
to support the weight and expansion forces of the heater.
Consider that the heater will expand in length as much as 1/2 inch (12.5 mm) or more for every
10 ft (3 m) of system length –
typically the greater the firing rate, the greater the expansion.
Refer to Section 11
1)
Survey the available structural supports, considering the system configuration and heat re-
quirements of the area to establish the optimum heater location.
a)
Locating a heater directly under joists or beams, or installing supplemental steel support
rail or angle iron can substantially reduce labor and materials
2) In a Tube Kit package tubes with turbulators are labelled as to their location in the system.
Also refer to Section 8: TURBULATOR LENGTH & LOCATION
3) Tube system hangers must be located: A) straight in line; B) at a common height (level);
and C)
116” (295
cm) apart.
-
see Figures 9 & 10 next page
.
a)
NOTE: It is important that the tubes in the system are installed in alignment horizontally
(level) and vertically (in line) –
this will ensure system integrity
4)
Hardware with a minimum 100 lb. (45 kg) work load must be used at each heater suspen-
sion point. A #2 Lion Chain or equivalent is typically used for suspending the heater.
a)
Connect to the structure using typical hardware as illustrated in FIGURE 8 (below) or by
other mechanically sound means
b)
If rigid devices such as
3/8”
threaded rods are used for suspension, swing joints or other
means must be provided to allow for system expansion
-
approximately ½ inch to 1 inch
for every 10 ft (1 cm to 2.5 cm for every 3 m) of system length.
5)
Two types of hangers are provided to suspend the tube system –
see FIGURES 9 & 10
a)
Plate hangers support the tubes and reflectors at each end of the system
b)
Webbed hangers support tubes and reflectors at each tube junction
HOOK OR EYE
BOLT THROUGH
HOLE IN BEAM
BEAM CLAMP
WITH HOOK OR
EYE
HOOK OR
EYE
SCREW
PIPE RING
OR CLEVIS
HANGER
BAR
-
JOIST
CLAMP
FIGURE 8 TYPICAL MOUNTING HARDWARE
NOTE: It is the installer
’
s responsibility to ensure that mounting hardware and