39
C
ONFIGURING THE
UPS
FROM DISPLAY
Configurations which can be modified by the user from the display are listed in
Table 2
(below).
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
ACCESS
LEVEL
Language
Selection of the mimic
panel language
English
English
Italian
German
French
Spanish
“PowerUser”
Homepage timeout
Selection of the screen
saver timeout
5 min.
1-240 minutes
“PowerUser”
Buzzer
Disables the
alarm buzzer
ON
OFF
ON
“PowerUser”
Date and time
UPS internal clock setup
-
-
“PowerUser”
Operating mode
Selection from among five
different operating modes
ON LINE
ON LINE
ECO
FREQUENCY CONVERTER
SMART ACTIVE
STAND-BY OFF
“Expert”
Battery low
Estimated autonomy time
remaining for “battery low”
warning
3 min.
1-7 @ 1 min step
“Expert”
Auto Restart
Enables the auto restart
function
5 sec.
OFF
ON (configurable 0-240 seconds)
“Expert”
Auto Power Off
Enables and configures
the auto power off function
OFF
OFF
ON (configurable 2-10%)
“Expert”
Output voltage
Selection of the output
voltage
(Phase - Neutral)
230V
220-240V (custom)
208V
200V
“Expert”
Output frequency
Selection of the inverter
frequency
50Hz
50Hz
60Hz
“Expert”
Automatic battery
test
Enables and schedules the
automatic battery test
40 h
OFF
ON (programmable)
“Expert”
User
password change
Replacement of the current
password with a new one
-
Any combination of characters for a
maximum of 16
“User”
“PowerUser”
password change
Replacement of the current
password with a new one
-
Any combination of characters for a
maximum of 16
“PowerUser”
“Expert”
password change
Replacement of the current
password with a new one
Expert
Any combination of characters for a
maximum of 16
“Expert”
Table 2
– UPS configuration (available from display)
D
EFAULT SETTING FOR OTHER PARAMETERS
In the
Table 3
(below) is listed the default setting for other parameters.
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Power Walk-In
Delay
Delay time of the UPS Power Walk-In
3 sec.
0 - 120 seconds
Power Walk-In
Duration
The duration of the transition mode
Disabled
1 - 120 seconds
Stand-by off
Delay
Delay between the mains comeback and the
output UPS switching off
0 sec.
0 - 3600 seconds
Table 3
– Default settings for other parameters (not available from display)