Transformer compensation
The compensation of a transformer for which no fixed stage is available can be solved in two ways with
the CX plus:
S
ETTING OF THE REACTIVE POWER OFFSET
The current transformer is installed at the output side of the transformer
consequently, the reactive
power of the transformer is not measured by the CX plus.
By setting an offset reactive power = reactive power of the transformer (SETUP/312), this is added to
the measured reactive power (within the system).
Procedure:
Determine the inductive reactive power of the transformer. Enter the determined value in the SETUP
menu
“312” in order to also compensate the transformer.
Function:
The set offset reactive power (Q offset) is added to the measured reactive power and considered in the
control deviation. Therefore, the cos
is always shown before the transformer. This means, that the
cos
within the system may be capacitive, but the measurement of the electrical power supplier
measures the required cos
.