SRB402EM

SRB402EM/CC

Operating instructions

Output expander module

EN

Dimensions H x W x D: 

SRB402EM: 120 × 22.5 × 121 mm 

SRB402EM/CC: 130 × 22.5 × 121 mm

The data specified in this manual are applicable when the  

component is operated with rated operating voltage U

e

 ±0%.

2.5  Safety classification

Standards:

 

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL:

 

up to e

Control category:

 

up to 4

DC: 

99% (high)

CCF:

 

> 65 points

PFH value: 

≤ 2.0 x 10

-8

/h

SIL:

 

up to 3

Service life: 

20 years

The PFH value of 2.0 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching 

cycles (n

op/y

) mentioned in the table below. At 365 operating days per 

year and a 24-hours operation, this results in the below-mentioned 

switching cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 

and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 

SRB402EM: 120 × 22.5 × 121 mm

SRB402EM/CC: 130 × 22.5 × 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 

against unintentional contact of the connected and therefore 

electrically interconnected apparatus and the insulation of the 

feed cables must be designed for the highest voltage, which 

can occur in the device.

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

• K1/K2: status channels 1 and 2

5.2  Description of the terminals

Voltages: A1

A2

+24 VDC/24 VAC
0 VDC/24 VAC

Outputs: 13-14

23-24
33-34
43-44
51-52
61-62

First safety enabling circuit
Second safety enabling circuit
Third safety enabling circuit
Fourth safety enabling circuit
Auxiliary NC contact as signalling contact
Auxiliary NC contact as signalling contact

Start:

X1-X2

Feedback circuit

Signalling outputs must not be used in safety circuits.

K1/K2

SRB 

402EM

13 23 33 43
A1 X1 51 61

14 24 34 44

A2 X2 52 62

Fig. 1

Содержание SRB402EM

Страница 1: ...eloped to execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant The output expander module must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding th...

Страница 2: ...and 43 44 meet the following requirements under observation of a PFH value assessment also refer to chapter 2 5 Safety classification Control category 4 PL e to DIN EN ISO 13849 1 Corresponds to SIL 3 to DIN EN 61508 2 SILCL 3 to DIN EN 62061 To determine the Performance Level PL of the entire safety function e g sensor logic actuator to DIN EN ISO 13849 1 an analysis of all relevant components is...

Страница 3: ... enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D SRB402EM 120 22 5 121 mm SRB402EM CC 130 22 5 121 mm 4 Electrical connection 4 1 General information for electrical connection As far as the electrical safety is concerned the protection against unintentional contact of the connected and therefo...

Страница 4: ...be disassembled in the de energised condition only Push up the bottom of the enclosure and hang out slightly tilted forwards 7 2 Disposal The output expander module must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations 8 Appendix 8 1 Wiring example Single channel control at terminal A1 of the SRB402EM expander module through a safety release of...

Страница 5: ...age Directive EMC Directive RoHS Directive 2006 95 EC 2004 108 EC 2011 65 EU 2014 35 EU 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2004 AC 2005 A1 2009 Place and date of issue Wuppertal April 13 2016 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Internet www schmersal com We he...

Страница 6: ...o KG Industrielle Sicherheitsschaltsysteme Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Отзывы: