Operating instructions
Safety-monitoring module

SRB301HC/T-24V

SRB301HC/T-230V

EN

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 
The following conditions must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3. Check the safety-monitoring module's enclosure for damage.
4.  Check the electrical function of the connected sensors and their influ-

ence on the safety-monitoring module and the downstream actuators

6.2  Maintenance

A regular visual inspection and functional test, including the following 
steps, is recommended:
1. Check the correct fixing of the safety-monitoring module
2. Check the cable for damages
3. Check electrical function

The device has to be integrated into the periodic check-ups 
according to the Ordinance on Industrial Safety and Health, 

however at least 1 × year.

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The safety-monitoring module must be disassembled in a de-energised 
condition only. Push up the bottom of the enclosure and hang out 
slightly tilted forwards.

7.2  Disposal

The safety-monitoring module must be disposed of in an appropriate 
manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring examples

Dual-channel control, shown for a guard door monitor; with two 
contacts A and B, where at least one is a positive break contact; 
with external reset button 

J

 (see Fig. 3)

•  Relay outputs: Suitable for 2-channel control, for increase in capacity 

or number of contacts by means of contactors or relays with positive-
guided contacts.

•  The control system recognises wire-breakage and earth faults in the 

monitoring circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

A1

S13

S14 S23

J

S24

X1

X2

K

B

K

A

K

A

K

B

K2

K1

A2

14

N

24

34

42

S

K2

a)

K1

ON

OUT

IN A

IN B

F1

13

23

33

L1

41

K

B

K

A

Fig. 2
a) Logic
 

S

 = Feedback circuit