2

Operating instructions

Safety-monitoring module

SRB NA-R-C.15

EN

The information contained in this operating instructions manual is pro-

vided without liability and is subject to technical modifications.

The entire concept of the control system, in which the 

safety component is integrated, must be validated to 

EN ISO 13849-2.

There are no residual risks, provided that the safety instructions as well 

as the instructions regarding mounting, commissioning, operation and 

maintenance are observed.

1.6  Warning about misuse

In case of improper use or manipulation of the safety 

switchgear, personal hazards or damages to machinery 

or plant components cannot be excluded. The relevant 

requirements of the standards EN 1088 and EN ISO 13850 

must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages result-

ing from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary re-

pairs, conversions and modifications to the device are strictly forbidden; 

the manufacturer shall accept no liability for damages resulting from 

such invasive work, arbitrary repairs, conversions and/or modifications 

to the device.

The safety-monitoring module must only be used when the enclosure is 

closed, i.e. with the front cover fitted.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

SRB NA-R-C.15 24VDC

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and therefore 

the compliance with the Machinery Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Destination and use

The safety-monitoring modules for integration in safety circuits are 

designed for fitting in control cabinets. They are used for the safe 

evaluation of the signals of positive break position switches for safety 

functions on sliding, hinged and removable safety guards as well as 

emergency stop control devices.

The safety function is defined as the opening of the enabling circuits  

13-14, 23-24 and 33-34 when the supply voltage C is disconnected. 

The safety-relevant current paths with output contacts 13-14, 23-24 and 

33-34 meet the following requirements under observation of a B

10d

 value 

assessment (also refer to “Requirements of DIN EN ISO 13849-1“):

– Control category 4 - PL e to DIN EN ISO 13849-1 

– SIL 3 to DIN EN 61508-2 

–  SILCL 3 to DIN EN 62061 (meets the requirements  

of control category 4 to DIN EN 954-1)

To determine the Performance Level (PL) of the entire safety function 

(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all 

relevant components is required.

2.4  Technical data

General data: 

Standards:

 

IEC/EN 60204-1, EN 60947-5-1;  

EN ISO 13849-1, IEC/EN 61508

Climate resistance:

  

EN 60068-2-78

Mounting:  

Snaps onto standard  

DIN rail to EN 60715

Terminal designations:

  

EN 60947-1

Material of the housings:  

Thermoplastic

Material of the contacts: 

AgSnO, self-cleaning,  

positive drive

Weight:

  

190 g

Start conditions:

 

Automatic or start button

Feedback circuit (Y/N):

 yes

Drop-out delay in case of emergency stop:

 

typ. 30 ms 

Pull-in delay:

 

typ. 10 ms 

Mechanical data: 

Connection type:

 

Screw connection

Cable section:

 

min. 0,25 mm² / max. 2,5 mm²

Connecting cable:

  

rigid or flexible

Tightening torque for the terminals:

  

0.6 Nm

With removable terminals (Y/N):

 Nein

Mechanical life: 

10 million operations

Electrical life:  

Derating curve  

available on request

Resistance to shock:

 

10 g / 11 ms

Resistance to vibrations to EN 60068-2-6:

 

10 ... 55 Hz,  

amplitude 0.35 mm

Ambient conditions: 

Ambient temperature:

 

– 25 °C … +45 °C

Storage and transport temperature:

 

– 40 °C … +85 °C

Protection class: 

Enclosure: IP40  

Terminals: IP20  

Clearance: IP54

Air clearances and creepage  

 

distances to IEC/EN 60664-1:

 

4 kV/2 (basic insulation)

EMC rating:  

to EMC Directive

Electrical data: 

Contact resistance in new state:

 

max. 100 mΩ

Power consumption: 

max. 2.5 VA

Rated operating voltage U

e

:

 

24 VDC –15% / +20%,  

residual ripple max. 10%

Max. fuse rating of the operating voltage:

 

T 1.0 A

Monitored inputs: 

Short-circuit recognition (Y/N): 

No

Wire breakage detection (Y/N):  

Yes

Earth leakage detection (Y/N):  

Yes

Number of NO contacts:

 0

Number of NC contacts:

 1

Cable length: 

1,500 m mit 1.5 mm² 

- 2,500 m mit 2.5 mm²  

1-channel

Conduction resistance:

 

max. 40 Ω