SRB-E-212ST / SRB-E-322ST

Operating instructions

Safety-monitoring module

EN

8.4  Setting report

This report regarding the setting of the device must be completed 

accordingly by the customer and enclosed in the technical 

documentation of the machine.

The setting report must be available whenever a safety check is 

performed.

Company:

The safety-monitoring module is used in the following machine:

Machine n°

Machine type

Module n°

Configured application (mode):

Set drop-out delay (t):

Set on (date)

Signature of the responsible person

8.5  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check the correct fixing of the safety-monitoring module

2. Check the cable for damages

3. Check electrical function

If a manual functional check is necessary to detect a 

possible accumulation of faults, then this must take place 

during the intervals noted as follows:

•  at least every month for PL e with category 3 or 

category 4 (according to ISO 13849-1) or SIL 3 with HFT 

(hardware fault tolerance) = 1 (according to IEC 62061);

•  at least every 12 months for PL d with category 3 

(according to ISO 13849-1) or SIL 2 with HFT (hardware 

fault tolerance) = 1 (according to IEC 62061).

Damaged or defective components must be replaced.

9.  Disassembly and disposal

9.1  Disassembly

The safety-monitoring module must be disassembled in a de-energised 

condition only.

9.2  Disposal

The safety-monitoring module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

10. 

Appendix

10.1 

Wiring/circuit information

Wiring example for cascading via safety input X7:

Safety outputs of following SRB-E modules can be switched off in each 

case via input X7.

For safety-orientated application, a fault in the wiring (short circuit to  

24 V potential) must be able to be excluded!

1

0

S11 S12 S21 S22

A1

A2

X3

X2

X7

Qt1

Y2

Y1

S

R

B

-E

-2

12

ST

24

23

14

13

Out 2

time[s]

RUN

ERR

ln 1

ln 2

Out 1

mode

1

0

S11 S12 S21 S22

A1

A2

X3

X2

Qt2

Qt1

X7

Y2

S

R

B

-E

-3

22

ST

24

23

14

13

42

41

34

33

time[s]

RUN

ERR

ln 1

ln 2

Out 1

Out 2

mode

Air clearances and creepage distances of the safety contacts:

1

0

S11 S12 S21 S22

A1

A2

X3

X2

X7

Qt1

Y2

Y1

S

R

B

-E

-2

12

ST

24

23

14

13

Out 2

time[s]

RUN

ERR

ln 1

ln 2

Out 1

mode

1

0

S11 S12 S21 S22

A1

A2

X3

X2

Qt2

Qt1

X7

Y2

S

R

B

-E

-3

22

ST

24

23

14

13

42

41

34

33

time[s]

RUN

ERR

ln 1

ln 2

Out 1

Out 2

mode

Against all other connection terminals, the safety contacts 13-14 and 

23-24 comply without additional measures with the requirements for 

double insulation in accordance with IEC 60664-1 and are to be used 

with switch voltages > 50 V. The safety contacts 33-34 comply with the 

requirements for basic insulation.

Содержание SRB-E-212ST

Страница 1: ...ure to comply with this warning notice could lead to physical injury and or damage to the machine Content 1 About this document 1 1 Function 1 1 2 Target group authorised qualified personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropriate use 2 1 5 General safety instructions 2 1 6 Warning about misuse 2 1 7 Exclusion of liability 2 2 Product description 2 1 Ordering code 2 2 2 Special ver...

Страница 2: ...pt no liability for damages resulting from the use of unauthorised spare parts or accessories For safety reasons invasive work on the device as well as arbitrary repairs conversions and modifications to the device are strictly forbidden the manufacturer shall accept no liability for damages resulting from such invasive work arbitrary repairs conversions and or modifications to the device The safet...

Страница 3: ...on category to IEC 60947 5 1 AC 15 230 V 4 A DC 13 24 V 4 A Switching capacity of the auxiliary contacts 41 42 24 VDC 1 A Fuse rating for the auxiliary contact safety fuse 2 5 A quick blow 2 A slow blow Safety contact values resistance max 100 mΩ AgNi self cleaning positive action Electrical life refer to 2 5 Mechanical life 10 million operations Semi conductor outputs Switching capacity of the sa...

Страница 4: ... for the relay contacts Diverging applications upon request Contact load nop y tcycle 20 880 000 0 6 min 40 330 000 1 6 min 60 110 000 5 0 min 80 44 000 12 0 min 100 17 600 30 0 min 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Hook bottom of enclosure in DIN rail and push down until it engages in position 3 2 Dimensions All measurements in mm Devi...

Страница 5: ...fety outputs STOP 0 Out 1 Outputs activated For flash code see section 5 4 Qt1 Qt2 Safety outputs STOP 1 Out 2 Outputs activated For flash code see section 5 4 1 0 S11 S12 S21 S22 A1 A2 X3 X2 X7 Qt1 Y2 Y1 SRB E 212ST 24 23 14 13 Out 2 time s RUN ERR ln 1 ln 2 Out 1 mode 1 0 S11 S12 S21 S22 A1 A2 X3 X2 Qt2 Qt1 X7 Y2 SRB E 322ST 24 23 14 13 42 41 34 33 time s RUN ERR ln 1 ln 2 Out 1 Out 2 mode Adjus...

Страница 6: ...e Rotary mode switch Rotary time switch System response LED indications RUN In 1 In 2 Out Factory setting Position 1 0 s Ready for application 1 Switch operating voltage on Position 1 Without connected sensors Lights up Turn to position C Application 1 is deleted Lights up Flashes Flashes Flashes Setting cycle active Application 1 is deleted No valid application stored Flashes SRB E ready for new ...

Страница 7: ...Continuously lit Not a valid application Flashes In 1 Input S12 closed Continuously lit Time window for synchronicity exceeded Flashes quickly Second channel input S22 has not opened Flashes slowly In 2 Input S22 closed Continuously lit Time window for synchronicity exceeded Flashes quickly Second channel input S12 has not opened Flashes slowly Out 1 Safety output STOP 0 ON Continuously lit No rel...

Страница 8: ...1 23 13 33 41 24 14 34 42 K1 K2 L1 KA KB N KC KD a b c d e f Key a Safety inputs b Safety outputs c Signalling outputs d Clock outputs e Processing f Power 7 2 Application example Dual channel control shown for a guard door monitor with two position switches where one has a positive break contact with external reset button J Relay outputs Suitable for 2 channel control for increase in capacity or ...

Страница 9: ...ther suitable measures X2 J S11 S21 X2 24VDC J Reset button detection of the trailing edge Reset without monitoring autostart Rotary knob position 1 Rotary knob position 6 Rotary knob position 2 Rotary knob position 7 Rotary knob position 3 Rotary knob position 8 Rotary knob position 4 Rotary knob position 9 Rotary knob position 5 Rotary knob position 10 7 4 Feedback circuit Release signal Suitabl...

Страница 10: ...ng autostart 8 Set up and maintenance 8 1 Commissioning The safety relay module features protection class IP54 for installation in a switch cabinet The safety relay module is delivered ready for operation Application 1 is preset in the factory 8 2 Functional testing The safety function of the safety monitoring module must be tested The following conditions must be previously checked and met 1 Corr...

Страница 11: ... must be replaced 9 Disassembly and disposal 9 1 Disassembly The safety monitoring module must be disassembled in a de energised condition only 9 2 Disposal The safety monitoring module must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations 10 Appendix 10 1 Wiring circuit information Wiring example for cascading via safety input X7 Safety output...

Страница 12: ...ny Internet www schmersal com We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives Name of the component SRB E 212ST SRB E 322ST Type See ordering code Description of the component Relay safety combination for emergency stop circuits guard door monitoring solenoid safety switches and AOPDs Relevant Direc...

Отзывы: