schmersal SRB 301LC/B-R Скачать руководство пользователя страница 4

4

Operating instructions

Safety-monitoring module

SRB 301LC/B

SRB 301LC/B-R

EN

If a manual functional check is necessary to detect a possible 

accumulation of faults, then this must take place during the 

intervals noted as follows:

•  at least every month for PL e with category 3 or category 

4 (according to ISO 13849-1) or SIL 3 with HFT (hardware 

fault tolerance) = 1 (according to IEC 62061);

•  at least every 12 months for PL d with category 3  

(according to ISO 13489-1) or SIL 2 with HFT (hardware 

fault tolerance) = 1 (according to IEC 62061).

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The safety-monitoring module must be disassembled in a de-energised 

condition only.

Push up the bottom of the enclosure and hang out slightly tilted 

forwards.

7.2  Disposal

The safety-monitoring module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring examples

Dual-channel control, shown for a guard door monitor with  

two position switches where one has a positive break contact; 

with external reset button 

J

 (Fig. 2)

•  Relay outputs: 2-channel control, suitable for increase incapacity or 

number of contacts by means of contactors or relays with positive-

guided contacts.

•  The control system recognises wire-breakage and earth faults in the 

monitoring circuit.

K

A

K

B

N

K2

K1

14 24 34 42

K2

a)

K1

Ui

F1

K

B

K

A

A2

A1

S12 S11

J

S21 S22 X1 X2

13 23

L1

S

K

B

K

A

33 41

Fig. 2

a) Logic

 S

 = Feedback circuit

8.2  Start configuration

External reset button (Fig. 3)

•  The external reset button is integrated in the feedback circuit in series.

•  The manual start or the activation of the module occurs when the 

button is pressed (not when it is released!).

Automatic start (see Fig. 4)

•  The automatic start is programmed by connecting the feedback  

circuit to the terminals X1-X2. If the feedback circuit is not required, 

establish a bridge.

• 

 Caution: Not admitted without additional measure due to the risk 

of gaining access by stepping behind!

•  When the safety-monitoring modules are used with the operating 

mode "Automatic start", an automatic restart after a shutdown in  

case of emergency must be prevented by the upstream control to  

EN 60204-1 paragraph 9.2.5.4.2.

K

B

J

S

K

A

X2

X1

K

B

S

K

A

X2

X1

Fig. 3

Fig. 4

8.3  Sensor configuration

Single-channel emergency stop circuit with command devices to 

ISO 13850 and EN 60947-5-5 (Fig. 5)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Category 1 – PL c to ISO 13849-1 possible.

Dual-channel emergency stop circuit with command devices to 

ISO 13850 and EN 60947-5-5 (Fig. 6)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  Control category 4 – PL e to ISO 13849-1 possible  

(with protective wiring)

Single-channel guard door monitoring circuit with interlocking 

devices to ISO 14119 (Fig. 7)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  Category 1 – PL c to ISO 13849-1 possible.

S12 S22

S12

S11

A

S12 S22

S11

S11

A

S12 S22

S12

S11

Fig. 5

Fig. 6

Fig. 7

Dual-channel guard door monitoring circuit with interlocking 

device to ISO 14119 (Fig. 8)

•  With at least one positive-break position switch

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  Control category 4 – PL e to ISO 13849-1 possible (with protective 

wiring)

Dual-channel control of magnetic safety switches to EN 60947-5-3 

(see Fig. 9)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  Category 3 – PL e to ISO 13849-1 possible.