schmersal SLC 420 IP 69 K Скачать руководство пользователя страница 6

6

EN

SLC 420 IP 69 K

Operating instructions

Safety light curtain

2.8.5 Contactor control (EDM)

The contactor control monitors the controlled switching elements 

(auxiliary contacts of the contactors) of both outputs This monitoring 

is realised after each interruption of the protection field and prior to the 

restart (enabling) of the outputs In this way, malfunctions of the relays 

are detected, eg contact welding or contact spring breakage If the 

light curtain detects a malfunctioning of the switching elements, the 

outputs are locked, ie after elimination of the failure, a Power Reset is 

required 

The auxiliary contacts must only be connected, when the 

function is activated!

After fault rectification, the operating voltage must be once switched off 

and back on (power reset)

The contactor control is not activated upon delivery This 

function is activated by means of the NSR-0801 BUS con-

verter and a PC or laptop

Activation of the contactor control (EDM) without software

The contactor control can be activated without PC software as of 

firmware version 123, by means of cable bridges (refer to wiring 

diagram)

2.8.6  Start interlock

The start interlock prevents an automatic start of the machine when the 

supply voltage is switched on After enabling of the start interlock - by 

the one-time interruption of the protection field -, this protective function 

is deactivated until the next power reset

The start interlock is not activated upon delivery This function 

is activated by means of the NSR-0801 BUS converter and a 

PC or laptop

2.9  Testing

The system performs a complete self-test and safety test within 2 sec-

onds after the operating voltage has been switched on If the protection 

field is not interrupted, the system switches to the ON condition In case 

of an error, the outputs at the receiver do not switch to the ON state 

The LED OSSD OFF starts flashing, thus emitting an error message 

Further indications can be found in the chapter Fault diagnostic

During operation, the system continuously executes a self-test Safety-

relevant faults are detected within the cycle time and cause the outputs 

to be switched off

2.10  Beam coding

The beam coding of the safety light curtain must be adjusted, when 

systems operating in each other's vicinity and a set-up as shown in the 

image below (no interference) is impossible When supplied, the beam 

coding is not active With beam coding A, a receiver can distinguish the 

beams of the transmitter with the same beam coding A, which are des-

tined to this particular receiver, from foreign beams The beam coding A 

must be set for each sensor (receiver and transmitter) individually The 

function is activated by means of the NSR-0801 BUS converter and a 

PC or laptop

If adjacent systems are operated without beam coding, the user is at 

risk

no interference

E

E

R

R

Interference: beam coding required!

E

R

R

E

•  The beam coding increases the safety and avoids mutual interference 

of adjacent systems

•  The beam coding increases the immunity against optical interference 

(eg sun light, welding sparks)

•  The beam coding A is permanently shown by the transmitter and the 

receiver by means of flashing LED's (refer to LED status information)

The response time of the system is increased when beam 

coding A is used To this end, the safety distance must be 

adjusted to the hazardous movement Refer to chapter 

Response time

3.  Mounting

3.1  General conditions

The following guidelines are provided as a  preventative warning notice 

to ensure safe and appropriate handling These guidelines are an 

essential part of the safety instructions and therefore must always be 

observed and respected

•  The SLC must not be used on machines, which can be 

stopped electrically in case of emergency

•  The safety distance between the SLC and a hazardous ma-

chine movement must always be observed and respected

•  Additional mechanical safety guards must be installed so 

that the operator has to pass by the protection field to reach 

the hazardous machine parts

•  The SLC must be installed so that the personnel always 

must be within the detection zone when operating the ma-

chine An incorrect installation can lead to serious injuries

•  Never connect the outputs to +24VDC If the outputs are 

wired to +24VDC, they are in ON state, as a result of which 

they are unable to stop a hazardous situation occuring on 

the application/machine

•  The safety inspections must be conducted regularly

•  The SLC must not be exposed to inflammable or explosive 

gasses

•  The connecting cables must be connected in accordance 

with the installation instructions

•  The fixing screws of the end caps and the mounting angle 

must be firmly tightened

•  When fitting the sensors, please observe that the cable 

output is at the bottom in order not to affect the functionality 

of the membrane

3.2  Protection field and approach

The protection field of the SLC consists of the entire range located 

between the protection field markings of transmitter and receiver Ad-

ditional protective devices must ensure that the operator has to pass by 

the protection field to reach the hazardous machine parts

The SLC must be installed so that personnel are always located within 

the detection zone of the safety device when operating the hazardous 

machine parts to be secure

Содержание SLC 420 IP 69 K

Страница 1: ...instructions are developed to execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the correct functional...

Страница 2: ...s result ing from the use of unauthorised spare parts or accessories For safety reasons invasive work on the device as well as arbitrary re pairs conversions and modifications to the device are strict...

Страница 3: ...olution 14 mm 0 3 10 0 m resolution 30 mm Response time 1 48 L 10 ms 49 144 L 20 ms without beam coding A 1 48 L 15 ms 49 144 L 27 ms with beam coding A Rated operating voltage 24 VDC 10 PELV supply u...

Страница 4: ...as Factory setting The SLC 420 system features many functions without additional devices The following table gives an overview of the possible functions and the factory settings configuration Function...

Страница 5: ...ombination of fixed and variable blanking is possible This function allows for an interruption of the protection height without the outputs being disabled in case of material movement in the protec ti...

Страница 6: ...iver from foreign beams The beam coding A must be set for each sensor receiver and transmitter individually The function is activated by means of the NSR 0801 BUS converter and a PC or laptop If adjac...

Страница 7: ...y guard Approach speed Resolution of the safety light curtain Safety light curtain SLC 420 The safety distance for resolutions 14 mm up to 40 mm is calculated by means of the following formula 1 S 200...

Страница 8: ...13855 and EN ISO 13857 3 4 1 Minimum distance to reflecting surfaces During the installation the effects of reflecting surfaces must be taken into account In case of an incorrect installation interru...

Страница 9: ...0 587 635 671 SLC 420 E R0570 xx 69 RFB 570 667 715 751 SLC 420 E R0650 xx 69 RFB 650 747 795 831 SLC 420 E R0730 xx 69 RFB 730 827 875 911 SLC 420 E R0810 xx 69 RFB 810 907 955 991 SLC 420 E R0890 xx...

Страница 10: ...RD 24 VDC BN 0 VDC BU OSSD 1 GN OSSD 2 YE Earth connection Restart interlock manual reset bridge 1 By bridging DIAG IN pin 5 and DIAG OUT pin 6 the restart interlock manual reset is activated Protecti...

Страница 11: ...r times 6 Power OFF 7 Remove cable bridges PIN 2 3 4 and if necessary cable bridge PIN 5 6 8 Wire OSSD 1 2 pin 3 4 9 Power ON To reverse the EDM function repeat the procedure step 2 7 If the programmi...

Страница 12: ...nery parts can only be accessed by passing through the protection field of the SLC 4 The staff remains within the detection area when works are con ducted on hazardous machinery parts 5 The safety dis...

Страница 13: ...D restart continuous flashing Wiring error for function selection Restart interlock manual reset automatic mode Check connection at the receiver bridge 1 or bridge 2 must be wired refer to Wiring 1 fl...

Страница 14: ...accordance with the national prescriptions and legislations 8 Appendix 8 1 Contact Consultancy Sales K A Schmersal GmbH Industrielle Sicherheitsschaltsysteme M ddinghofe 30 D 42279 Wuppertal Tel 49 0...

Страница 15: ...rson authorized for the compilation of the technical documentation Ulrich Loss M ddinghofe 30 42279 Wuppertal Notified body for the prototype test T V Nord Cert GmbH Langemarckstr 20 45141 Essen ID n...

Страница 16: ...Safety Control GmbH Am Industriepark 33 D 84453 M hldorf Inn Telefon 49 0 86 31 187 9 60 Telefax 49 0 86 31 187 9 61 E Mail info safetycontrol com...

Отзывы: