SLC 420 IP 69 K
Operating instructions
Safety light curtain
2.6 Response time (reaction time)
The response time depends on the hight of the protected field, the
resolution, the number of light beams and the beam coding
Resolution 14 mm
Protected
height
[mm]
Beams
[Number]
Response
time
[ms]
Response time
with beam cod-
ing A
[ms]
Weight
[kg]
170
16
10
15
16
250
24
10
15
19
330
32
10
15
23
410
40
10
15
26
490
48
10
15
30
570
56
20
27
33
650
64
20
27
37
730
72
20
27
41
810
80
20
27
45
890
88
20
27
48
970
96
20
27
52
1050
104
20
27
56
1130
112
20
27
60
1210
120
20
27
64
1290
128
20
27
68
1370
136
20
27
72
1450
144
20
27
76
Resolution 30 mm
Protected
height
[mm]
Beams
[Number]
Response
time [ms]
Response time
with beam cod-
ing A
[ms]
Weight
[kg]
170
8
10
15
16
250
12
10
15
19
330
16
10
15
23
410
20
10
15
26
490
24
10
15
30
570
28
10
15
33
650
32
10
15
37
730
36
10
15
41
810
40
10
15
45
890
44
10
15
48
970
48
10
15
52
1050
52
20
27
56
1130
56
20
27
60
1210
60
20
27
64
1290
64
20
27
68
1370
68
20
27
72
1450
72
20
27
76
2.7 Safety classification
Standards:
EN ISO 13849-1, EN 62061
PL:
up to e
Control category:
up to 4
PFH value:
742 x 10
-9
/ h
SIL:
up to 3
Service life:
20 years
2.8 Functions
The system consists of a receiver and a transmitter For the described
functions, no further switching elements are required For the diagnostics
and function selection, a user-friendly PC-software is offered as accessory
For the connection to a PC, the NSR-0801 BUS converter is required
(not included in delivery)
The system has the following features:
• Protective mode (automatic start after release of the protected field)
• Start interlock
• Restart interlock (manual reset)
• Contactor control EDM
• Beam coding
• Blanking of fixed protection field areas
• Blanking of movable protection field areas
Factory setting
The SLC 420 system features many functions without additional
devices The following table gives an overview of the possible functions
and the factory settings configuration
Function
Factory set-
ting
Configuration
Protective mode
not active
External wiring
Restart interlock
(manual reset)
not active
External wiring
Blanking fixed/vari-
able
not active
With BUS converter NSR-
0801 and PC-software
Contactor control
not active
With BUS converter NSR-
0801 and PC-software
Start interlock
not active
With BUS converter NSR-
0801 and PC-software
Beam coding
not active
With BUS converter
NSR-0801 and PC-software
2.8.1 Protective mode
The protective mode switches the OSSD outputs to ON state (protec-
tion field not interrupted), without external release of a switching device
This type of protection generates an automatic restart of the machine if
the protection field is not interrupted
This operating mode may only be chosen in conjunction with
the restart interlock (manual reset) of the machine
This operating mode must not be chosen, when persons can
step behind the protection field
2.8.2 Restart interlock (manual reset)
The restart interlock (manual reset) prevents an automatic enabling of
the outputs (OSSD's ON state) after switch-on of the operating volt-
age or an interruption of the protection field The system switches the
outputs only to ON state, when an external command device (restart
button) generates an enabling signal at the restart input (receiver)
The command devices (enabling button) must be installed
outside of the hazardous area The operator must have a
clear view on the hazardous area when actuating the ena-
bling button
In supply condition, the restart interlock (manual reset)
neither the protective mode is active You must choose one of
both operating modes to enable the OSSD outputs If no type
of protection is selected, you will obtain the following signali-
sation through the LED status indication in the receiver:
LED OSSD OFF (red) + LED restart (yellow) flashing