schmersal SLC 220 Скачать руководство пользователя страница 12

12

Operating instructions

Safety light curtain / safety light grid

SLC 220

SLG 220

EN

6.  Diagnostic

6.1  LED status information

Transmitter

Receiver

IR power

Restart interlock (manual reset)

External test / blanking

ON

OFF

Signal quality

Function

LED colour Description

Function LED colour Description

IR power

orange

IR transmitter active, signaled by continuous 
signal

ON

green

OSSD's ON state system check OK, 
activated protection field clear, signaled 
by continuous signal

Restart inter-
lock (manual 
reset)

yellow

Request signal at input restart interlock, signaled 
by continuous signal

OFF

red

OSSD's OFF state, active protection 
field interrupted - continuous signal; 
connection with NSR-0700 or diagnostic 
flag - flashing

External test / 
blanking

green

Blanking active, signaled by flashing, test signal 
active, signaled by continuous signal

Signal 
quality

orange

Insufficient signal reception, signaling 
depending on the signal quality

6.2  Fault diagnostic

The light grid performs an internal self-test after the operating voltage is switched on and the protection field is enabled. When a fault is detected, a 

corresponding flashing pattern is emitted at the receiver through the LED OSSD OFF (red). Every fault emission is followed by a one-second pause.

LED OSSD OFF 

Fault feature

Action

OSSD OFF and LED re-
start continuous flashing

If the function contactor control is activated and no state 
change has been detected at the contactor control input 
after enabling of the OSSD.

- Check contactor control connection
-  Check the connected contactor for closed contact (if 

OSSD ON - contactor control input must show GND level, 
if OSSD OFF - contactor control input must show +24V) 

- Switch-on only after POWER OFF/ON

1 flashes

Receiver configuration error or communication error

- Check transmitter and receiver configuration
- reparameterize (factory setting) with additional software
- Replace receiver

2 flashes

Transmitter configuration error or communication error

- Check transmitter and receiver configuration
- Check transmitter/receiver protection field
- Check transmitter/receiver connection
- Replace transmitter

3 flashes

Error during the OSSD test
Voltage is detected during the OSSD test, although the 
OSSD are in OFF state.

-  Check the connecting cables of the OSSD outputs for 

short-circuits at + U

b

 (cables, connected devices)

- Replace receiver

4 flashes

The cascaded receiver unit is not correctly connected or 
is defective.

-  Check connection and configuration of the cascaded 

receiver (protection field height and resolution)

- Replace cascaded system receiver

5 flashes

The cascaded transmitter unit is not correctly connected 
or is defective.

-  Check connection and configuration of the cascaded trans-

mitter (protection field height and resolution)

- Replace cascaded system transmitter

6.3  Extended diagnostic

By means of the optional configuration software and the NSR-0700 

BUS converter, an extended diagnostic can be executed. The software 

provides the status information of the component and can represent the 

individual light lines. This feature enables an optimal adjustment of the 

light curtain. The diagnostic mode is signalled by the OSSD ON and 

OSSD OFF LED‘s at the receiver. In diagnostic mode, protective mode 

is disabled, the ODDS outputs being locked. The change from diagnos-

tic mode to protective mode is automatically realised after Power Reset, 

when the BUS converter is no longer integrated and the connecting 

cable of the sensor is reconnected.

Содержание SLC 220

Страница 1: ...ct description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailin...

Страница 2: ...nge 0 3 m 6 m H Range 5 m 30 m high range M Master function S Slave function Only if the information described in this operating instruc tions manual are realised correctly the safety function and the...

Страница 3: ...l reset 20 ms 1 0 s signal trans mission in case of trailing edge Start interlock 250 ms 1500 ms adjustable LED indications transmitter Transmitting status restart LED indications receiver OSSD ON OSS...

Страница 4: ...ton 2 8 3 Fixed blanking The SLC 220 can blank stationary parts in the protection field Multiple protection field areas can be blanked Fixed blanking area E1 R1 The range of the fixed blanking can be...

Страница 5: ...nsion is possible up to max 96 lines and a pro tection field height of 2 45 m with the same resolution The connection of the systems master and slave is realised with the pre wired connector KA 0907 3...

Страница 6: ...the following elements Stopping time of the machine calculation by run on time measure ment Response time of the machine and the safety light curtain and the downstream relay entire safety guard Appr...

Страница 7: ...41 mm The following mounting heights to EN 999 must be observed Number of beams Mounting height above reference floor Floor in mm 2 400 900 3 300 700 1100 4 300 600 900 1200 The successor standards of...

Страница 8: ...2 1289 1 8 SLC 220 E R1375 30 RFB 1375 0 8 1422 1 5 1439 2 0 SLC 220 E R1525 30 RFB 1525 0 8 1572 1 5 1589 2 0 SLC 220 E R1675 30 RFB 1675 0 8 1722 1 5 1739 2 0 All versions with resolution 30 and 80...

Страница 9: ...fety light curtain safety light grid EN Accessories Mounting kit MS 1000 5 5 5 14 25 39 27 46 5 5 8 35 20 Centre support MS 1010 3 8 19 1 42 4 38 1 38 1 43 2 46 5 27 20 30 43 12 8 19 2 5 5 3 5 R 2 5 C...

Страница 10: ...RS485 B grey 24V brown 0V blue RS485 A pink RS485 B grey Signal quality white 24V brown 0V blue OSSD2 yellow OSSD1 green Earth connection Restart interlock active this connection is omitted connect S2...

Страница 11: ...ies Conditions For safety reasons all inspection results must be archived The operat ing principle of the SLC SLG and the machine must be known in order to be able conducting an inspection If the fitt...

Страница 12: ...D OFF contactor control input must show 24V Switch on only after POWER OFF ON 1 flashes Receiver configuration error or communication error Check transmitter and receiver configuration reparameterize...

Страница 13: ...manner in accordance with the national prescriptions and legislations 8 Appendix 8 1 Contact Consultancy Sales K A Schmersal GmbH Industrielle Sicherheitsschaltsysteme M ddinghofe 30 D 42279 Wuppertal...

Страница 14: ...h Loss M ddinghofe 30 42279 Wuppertal Notiied body for the prototype test T V Nord Cert GmbH Langemarckstr 20 45141 Essen ID n 0044 EC prototype test certiicate n 44 205 10 555867 004 Safety Control G...

Отзывы: