background image

5

EN

SLC 220 IP 69 K

SLG 220 IP 69 K

Operating instructions

Safety light curtain / safety light grid

2.8.5 Start interlock

The start interlock prevents an automatic start of the machine when the 

supply voltage is switched on. After enabling of the start interlock - by 

the one-time interruption of the protection field -, this protective function 

is deactivated until the next power reset.

The start interlock is not activated upon delivery. This function 

is activated by means of the NSR-0700 BUS converter and a 

PC or laptop.

2.8.6 Testing

The system performs a complete self-test within 2 seconds after the 

operating voltage has been switched on. After this self-test, the system 

switches to the ON state, if the protection field is clear.

The system will check all safety-technical functions in the 

background within a cycle time of 2 seconds. Within this time, 

a check of all functional components as well as a complete 

memory test will take place. The main advantage for the user 

is the omission of the system test (test before each machine 

cycle). 

In this operating mode, both outputs (OSSD1 and OSSD2) must be 

integrated in the application, separated from each other (second switch-

off path - refer to wiring diagram 4.1).

External test

The system can trigger a test cycle by means of the external test input. 

By applying a signal (+ +24 VDC) at the test output, a complete self-test 

is executed within 150 ms. After 15 ms, the outputs change to OFF 

state and are re-enabled after 150 ms if no fault is detected. The test 

cycle must be triggered by the machine control. The signal change at 

the outputs of the SLC/SLG 220 series must be monitored. In case of a 

fault, the outputs will not be re-enabled until the fault is rectified.

If the test cycle of the application/machine cannot be comple-

ted within 150 ms, the restart interlock of the SLC/SLG 220 

series must be activated (refer to wiring diagram 4.1). The 

max. test time of 150 ms must be observed to the standard 

EN 61496.

3.  Mounting

3.1  General conditions

The following guidelines are provided as preventive warning notices 

to ensure a safe and appropriate handling. These guidelines are an 

essential part of the safety instructions and therefore must always be 

observed and respected.

•  The SLC/SLG must not be used on machines, which can be 

stopped electrically in case of emergency.

•  The safety distance between the SLC/SLG and a hazardous 

machine movement must always be observed and respec-

ted.

•  Additional mechanical safety guards must be installed so that 

the operator has to pass by the protection field to reach the 

hazardous machine parts.

•  The SLC/SLG must be installed so that the personnel always 

must be within the detection zone when operating the machi-

ne. An incorrect installation can lead to serious injuries.

•  Never connect the outputs to +24VDC. If the outputs are 

wired to +24VDC, they are in ON state, as a result of which 

they are unable to stop a hazardous situation occuring on the 

application/machine.

•  The safety inspections must be conducted regularly.

•  The SLC/SLG must not be exposed to inflammable or explo-

sive gasses.

•  The connecting cables must be connected in accordance 

with the installation instructions.

•  The fixing screws of the end caps and the mounting angle 

must be firmly tightened.

•  When fitting the sensors, please observe that the cable 

output is at the bottom in order not to affect the functionality 

of the membrane.

3.2  Protection field and approach

The protection field of the SLC/SLG consists of the entire range located 

between the protection field markings of transmitter and receiver. Addi-

tional protective devices must ensure that the operator has to pass by 

the protection field to reach the hazardous machine parts.

The SLC/SLG must be installed so that the personnel is always located 

within the detection zone of the safety device when operating the hazar-

dous machine parts to be secured.

Содержание SLC 220 IP 69 K

Страница 1: ...ymbols used Information hint note This symbol is used for identifying useful additional informa tion Caution Failure to comply with this warning notice could lead to failures or malfunctions Warning Failure to comply with this warning notice could lead to physical injury and or damage to the machine 1 4 Appropriate use The products described in these operating instructions are developed to execute...

Страница 2: ...ld heights in mm available lengths 0175 0250 0325 0475 0625 0775 0925 1075 1225 1375 1525 1675 30 80 Resolution 30 80 mm Range 0 3 m 6 m H Range 4 m 14 m high range only for resolution 30 mm SLG 220 E R 69 RF No Option Description Distance between outermost beams 0500 02 500 mm 2 beam 0800 03 800 mm 3 beam 0900 04 900 mm 4 beam Range 0 3 m 6 m H Range 5 m 30 m high range Only if the information de...

Страница 3: ...IGH 11 120 mA Input current LOW 0 2 mA Function SLC 220 Protective mode start and restart interlock contactor control fixed beam blanking SLG 220 start and restart interlock contactor control Signal times Contactor control 20 300 ms Restart interlock manual reset 20 ms 1 0 s signal trans mission in case of trailing edge Start interlock 250 1500 ms adjustable LED indications transmitter Transmittin...

Страница 4: ...he hazardous area The operator must have a clear view on the hazardous area when actuating the enab ling button 2 8 3 Fixed blanking The SLC 220 can blank stationary parts in the protection field Multiple protection field areas can be blanked Fixed blanking area E1 R1 The range of the fixed blanking can be arbitrarily chosen in the protec tion field Multiple areas can be blanked At least one light...

Страница 5: ... series must be activated refer to wiring diagram 4 1 The max test time of 150 ms must be observed to the standard EN 61496 3 Mounting 3 1 General conditions The following guidelines are provided as preventive warning notices to ensure a safe and appropriate handling These guidelines are an essential part of the safety instructions and therefore must always be observed and respected The SLC SLG mu...

Страница 6: ...d Approach speed Resolution of the safety light curtain Safety light curtain SLC 220 The safety distance for resolutions 14 mm up to 40 mm is calculated by means of the following formula S 2000 mm s T 8 d 14 mm S Safety distance mm T Total reaction time machine stopping time reaction time of the safety guard relays etc d Resolution of the safety light curtain The approach speed is covered with a v...

Страница 7: ...the EN 999 for calculating the minimum distances of the safety guards with regard to the hazardous point are EN ISO 13855 and EN ISO 13857 The safety distance between the safety light grid and the hazardous point must always be respected and observed If a person reaches the hazardous point before the hazardous movement has come to standstill he she is exposed to seri ous injuries 3 4 1 Minimum dis...

Страница 8: ...1429 1477 1513 SLC 220 E R1525 xx 69 RFB 1525 1579 1627 1663 SLC 220 E R1675 xx 69 RFB 1675 1729 1777 1813 All versions with resolution 30 and 80 mm as well as variant H range from 4 0 to 14 0 m have identical dimensions with the same protection field height For the SLC 220 E R0175 30 69 RFB type the dimension changes from 23 mm to 35 5 mm due to the extended profile length The protec tion field i...

Страница 9: ...9 EN SLC 220 IP 69 K SLG 220 IP 69 K Operating instructions Safety light curtain safety light grid Accessories Fixing kit MS 1035 14 5 42 18 9 20 6 5 40 32 52 ...

Страница 10: ... outputs OSSD 1 OSSD 2 kn1 kn2 Auxiliary contacts of the last switching relay for contactor control optional S1 Command device for external test optional S2 Command device for restart interlock manual reset enabling E1 Power supply 24 VDC 10 RS 485 A B These connections between the transmitter and the receiver are required for the operation 4 2 Connector configuration Receiver Emitter possibly acc...

Страница 11: ...ns please make sure that the user has the necessary information at his disposal to be able conducting the maintenance 5 3 Regular check A regular visual inspection and functional test including the following steps is recommended 1 The component does not have any visible damages 2 The optics cover is not scratched or soiled 3 Hazardous machinery parts can only be accessed by passing through the pro...

Страница 12: ...ture Action OSSD OFF and LED re start continuous flashing If the function contactor control is activated and no state change has been detected at the contactor control input after enabling of the OSSD Check contactor control connection Check the connected contactor for closed contact if OSSD ON contactor control input must show GND level if OSSD OFF contactor control input must show 24V Switch on ...

Страница 13: ...mode is automatically realised after Power Reset when the BUS converter is no longer integrated and the connecting cable of the sensor is reconnected 7 Disassembly and disposal 7 1 Disassembly The safety switchgear must be disassembled in a de energised condi tion only 7 2 Disposal The safety switchgear must be disposed of in an appropriate manner in accordance with the national prescriptions and ...

Страница 14: ...entation Ulrich Loss Möddinghofe 30 42279 Wuppertal Notiied body for the prototype test TÜV Nord Cert GmbH Langemarckstr 20 45141 Essen ID n 0044 EC prototype test certiicate n 44 205 10 555867 004 Safety Control GmbH Am Industriepark 33 D 84453 Mühldorf Inn Telefon 49 0 86 31 187 9 60 Telefax 49 0 86 31 187 9 61 E Mail info safetycontrol com Place and date of issue Wuppertal February 1 2010 Autho...

Отзывы: