EX-AZM 415

Operating instructions

Solenoid interlock

EN

3.  Mounting

3.1  General mounting instructions

Fitting is only authorised in a de-energised condition.  

The enclosure must be mechanically protected.

Four mounting holes are provided for fixing the enclosure. The use of 

a protective ground wire is imperative. The enclosure must not be used 

as an end stop.  Any mounting position. The mounting position must be 

chosen so as to avoid the penetration of dirt in the used holes.

Please observe the recommendations regarding maximum 

impact energy, actuating speed and tightening torque in the 

technical data. The distance between the actuator flange and 

the switch enclosure must be < 3 mm when the actuator is 

inserted.

Mounting of the actuators:

 See mounting instructions actuators.

The actuators AZ/AZM 415-B1, -B2 and -B3 are authorised for use in 

conjunction with the EX-AZM 415.

Please observe the relevant requirements of the standards 

ISO 12100, ISO 14119 and ISO 14120.

The safety component and the actuator must be permanently 

fitted to the safety guards and protected against displacement 

by suitable measures (tamperproof screws, gluing, drilling, 

pinning). 

3.2  Dimensions

All measurements in mm.

Solenoid interlock

29,5

46,5

8,6

¤

6,5

¤

11

24,5

88

130

114

M20 x 1,5

M20 x 1,5

A

100

24,7

84

28

Key

A

 setting screw: ball latch 80 - 400 N

4.  Rear side Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

The contact labelling can be found in the wiring compartment of the 

switch.

If the risk analysis indicates the use of a monitored interlock 

they are to be connected in the safety circuit with the contacts 

indicated with the symbol  .

Cable glands (included in delivery) are only authorised for permanent 

cables. The constructor must provide for the necessary strain relief. The 

conductors of the connecting cables must not obstruct the movement of 

the switching lever. Unused openings must be sealed with EX-certified 

locking screws (included in delivery).

4.2  Contact variants

Contacts shown in a de-energised condition and with the actuator 

inserted.

Power to unlock

EX-AZM 415-11/11ZPK…-3D

EX-AZM 415-11/02ZPK…-3D

S1

A2

A1

S2

23 11

24 12

13
21

14
22

Q

P

S1

A2

A1

S2

23 11

24 12

11
21

12
22

Q

P

EX-AZM 415-11/20ZPK…-3D

EX-AZM 415-02/11ZPK…-3D

S1

A2

A1

S2

13
23

14
24

Q

P

23 11

24 12

21  11

22 12

S1

A2

A1

S2

13
21

14
22

Q

P

EX-AZM 415-02/02ZPK…-3D

EX-AZM 415-02/20ZPK…-3D

21  11

22 12

S1

A2

A1

S2

11
21

12
22

Q

P

21  11

22 12

S1

A2

A1

S2

13
23

14
24

Q

P