Operating instructions

Safety switch

EX-AZ 415

EN

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

EX-AZ 415-

ZPK-

-3D

No. Option Description

S1

S2

11 / 11 1 NO Contact 1 NC contact 1 NO Contact 1 NC contact

02 / 11 2 NC

1 NO Contact 1 NC contact

02 / 20 2 NC

2 NO

02 / 02 2 NC

2 NC

1637

Gold-plated contacts

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and 

therefore the compliance with the Machinery Directive and 

the Explosion Protection Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Purpose

The safety switch has been designed to prevent, in conjunction with the 

control part of a machine, movable safety guards from being opened 

before hazardous conditions have been eliminated.

The safety switchgears are classified according to ISO 14119 

as type 2 interlocking devices. 

 The components can be used in explosion-endangered areas of Zone 

22 equipment category 3D. Installation and maintenance requirements 

to the standard series EN 60079 must be met.

The user must evaluate and design the safety chain in 

accordance with the relevant standards and the required 

safety level.

The entire concept of the control system, in which the safety 

component is integrated, must be validated to the relevant 

standards. 

Conditions for safe operation

Due to their specific impact energy, the components must be fitted 

with a protection against mechanical stresses. The specific ambient 

temperature range must be observed.

2.4  Technical data

Equipment category: 

L

 

II 3D

Ex protection:

 

Ex tc IIIC T60°C Dc X

Standards:

 

IEC 60947-5-1, EN 60079-0,  

EN 60079-31, BG-GS-ET-15

Enclosure:

 

light-alloy diecast, paint finish

Actuator:

 

zinc-plated brass / aluminium

Max. impact energy:

 

4 J

Actuating speed:

 

max. 1 m/s

Protection class: 

IP67 to IEC 60529

Contact material:

 Silver

Coding level according to ISO 14119: 

 low

Contact type: 

change-over with double break Zb,  

or 2 NC contacts, galvanically separated contact bridges

Switching system:

 

A

 IEC 60947-5-1; slow action,  

NC contact with positive break

Connection:

 

screw terminals

Cable section:

 

min. 0.75 mm² ... max. 1.5 mm²  

(including conductor ferrules)

Cable entry: 

2 x M20 x 1.5

Rated impulse withstand voltage U

imp

:

 

4 kV

Rated insulation voltage U

i

:

 

250 V

Thermal test current I

the

:

 

6 A

Utilisation category:

 

AC-15 / DC-13

Rated operating current/voltage I

e

/U

e

:

 

4 A / 230 VAC 4 A / 24 VDC

Max. fuse rating:

 

6 A gG D-fuse

Positive break travel:

 

3.8 mm

Positive break force: 

min. 31 N

Ambient temperature:

 

–10 °C … +50 °C

Mechanical life:

 

max. 1 million operations

Latching force: 

80 - 400 N (adjustable)

Cable gland and locking screws: 

L

 II 2GD

Cable cross-section of the cable glands: 

min. Ø 7 mm;  

max. Ø 12 mm

Tightening torques:

 

cover screws: min. 0.6 Nm 

Bottom cover screws: min. 0.7 Nm 

Cable gland: min. 8 Nm 

Locking screw: min. 8 Nm

2.5  Safety classification

Standards:

 

ISO 13849-1

Envisaged structure: 

 

- Basically: 

applicable up to Cat. 1 / PL c 

-  With 2-channel usage and  

 

fault exclusion mechanism*: 

applicable up to Cat. 3 / PL d  

with suitable logic unit

B

10D

 NC contact:

 2,000,000

B

10D

 NO contact at 10% ohmic contact load:

 1,000,000

Service life:

 

20 years

* If a fault exclusion to the 1-channel mechanics is authorised.

MTTF

B

d x

x

h

s/h

3600

D

10D

op

op

op

n

0,1 x n

op

t

cycle

(Specifications can vary depending on the application-specific 

parameters h

op

, d

op

, t

cycle

 as well as the load.)

If multiple safety components are wired in series, the Performance 

Level to ISO 13849-1 will be reduced due to the restricted error 

detection under certain circumstances.

Содержание EX-AZ 415

Страница 1: ...e with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations an...

Страница 2: ...ated must be validated to the relevant standards Conditions for safe operation Due to their specific impact energy the components must be fitted with a protection against mechanical stresses The specific ambient temperature range must be observed 2 4 Technical data Equipment category L II 3D Ex protection Ex tc IIIC T60 C Dc X Standards IEC 60947 5 1 EN 60079 0 EN 60079 31 BG GS ET 15 Enclosure li...

Страница 3: ...nnection The electrical connection may only be carried out by authorised personnel in a de energised condition The contact labelling can be found in the wiring compartment of the switch At least one magnetic contact A with positive break contacts must be integrated in the safety circuit Cable glands included in delivery are only authorised for permanent cables The constructor must provide for the ...

Страница 4: ...escribed above the component requires little maintenance For use in extreme conditions we recommend routine maintenance including the following steps 1 Check the correct fixing of the actuator and the safety switchgear 2 Remove particles of dust and soiling 3 Check cable entry and connections in a de energised condition Do not open the device when live Adequate measures must be taken to ensure pro...

Страница 5: ...quality assurance system referred to in Appendix IV 2014 34 EU TÜV Rheinland Industrie Service GmbH Am Grauen Stein 51105 Köln ID n 0035 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal May 2 2017 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmer...

Страница 6: ... A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Отзывы: