Operating instructions

Solenoid interlock

AZM 200

EN

There are no residual risks, provided that the safety instructions as well 

as the instructions regarding mounting, commissioning, operation and 

maintenance are observed.

1.6  Warning about misuse

In case of improper use or manipulation of the safety 

switchgear, personal hazards or damages to machinery 

or plant components cannot be excluded when safety 

switchgear is used. The relevant requirements of the 

standard ISO 14119 must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

AZM 200 

 

-T-

➂➃

No. Option

Description

Solenoid interlock monitored

B

Actuator monitored

SK

Screw connection

CC

Cage clamps

ST1

Connector plug M23, (8+1)-pole

ST2

Connector plug M12, 8-pole

1P2P

1 p-type diagnostic output and  

2 p-type safety outputs

1P2PW

similar to -1P2P, combined diagnostic signal guard 

door closed and solenoid interlock locked

SD2P

serial diagnostic output and 2 p-type safety outputs

Power to unlock

A

Power to lock

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and therefore 

the compliance with the Machinery Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Comprehensive quality insurance to 2006/42/EC

Schmersal is a certified company to appendix X of the Machinery 

Directive. As a result, Schmersal is entitled to autonomously conduct 

the conformity assessment procedure for the products listed in 

Appendix IV of the MD without involving a notified body. The prototype 

test certificates are available upon request or can be downloaded from 

the Internet at www.schmersal.com.

2.4  Destination and use

The AZM 200 with non-contact electronic safety sensors is designed for 

application in safety circuits and is used for monitoring the position of 

movable safety guards.

The safety function consists of safely switching off the safety outputs 

when the safety guard is unlocked or opened and maintaining the safe 

switched off condition of the safety outputs for as long as the safety 

guard is open.

For applications requiring a safe monitoring of the interlocking 

function, the AZM 200 ... variant must be selected. The AZM 

200 B ... is a safety switch with additional interlocking function.

Interlocks with power to lock principle may only be used in 

special cases after a thorough evaluation of the accident risk, 

since the safety guard can be opened immediately on failure 

of the power supply or upon activation of the main switch.

The safety switchgears are classified according to  

ISO 14119 as type 4 interlocking devices.

Series-wiring

Series-wiring can be set up. The response and risk times are not 

altered by wiring in series. The number of components is only limited  

by the external cable protection according to the technical data and  

the line loss. Up to 31 components can be wired in series.

In devices with the serial diagnostics function (ordering suffix -SD),  

the serial diagnostics connections are wired in series and connected 

to a SD Gateway for evaluation purposes.

Wiring examples for series-wiring, refer to appendix

The user must evaluate and design the safety chain in 

accordance with the relevant standards and the required 

safety level. If multiple safety switchgears are involved in 

the same safety function, the PFH values of the individual 

components must be added. 

The entire concept of the control system, in which the safety 

component is integrated, must be validated to the relevant 

standards.

2.5  Technical data

Standards:

 

IEC 60947-5-1, IEC 60947-5-3, ISO 14119,  

ISO 13849-1, IEC 61508, IEC 62061

Material of the enclosure:

 

glass-fibre reinforced thermoplastic, 

self-extinguishing

Mechanical life:

 

≥ 1 million operations

Holding force F:

 

2000 N 

(1000 N when used with the  

AZ/AZM 200-B30 actuator, for indoor use)

Coding levels according to ISO 14119: 

low

Latching force:

 

30 N

Protection class:

 

IP66, IP67 to IEC 60529

Insulation protection class:

 II, 

X

Overvoltage category:

 III

Degree of pollution:

 3

Execution of the electrical connection:

 

screw terminals or  

cage clamp connection,  

M12 or M23 connector

Cable section:

 

min. 0.25 mm², max. 1.5 mm²  

(including conductor ferrules)

Cable entry:

 M20

Tightening torque for the cover screws:

 

0.7 ... 1 Nm (Torx T10)

Series-wiring:

 

up to 31 devices

Cable length:

 

max. 200 m (Cable length and  

cable section alter the voltage drop  

depending on the output current)

Содержание AZM 200

Страница 1: ...e with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations an...

Страница 2: ...0 with non contact electronic safety sensors is designed for application in safety circuits and is used for monitoring the position of movable safety guards The safety function consists of safely switching off the safety outputs when the safety guard is unlocked or opened and maintaining the safe switched off condition of the safety outputs for as long as the safety guard is open For applications ...

Страница 3: ... 10 9 h PFD 2 2 x 10 4 SIL suitable for SIL 2 applications Service life 20 years The safety consideration of the guard locking function only applies for standard devices with monitored solenoid interlock AZM 200 1P2P W see Ordering code The actuation of the interlock must be compared with the external OSSD enabler If a shut down now occurs due to an unintentional unlocking this is detected by an e...

Страница 4: ...or is connected to electronic safety monitoring modules we recommend that you set a discrepancy time of 100 ms The safety inputs of the safety monitoring module must be able to blank a test impulse of approx 1 ms The safety monitoring module does not need to have a cross wire short monitoring function if necessary the cross wire short monitoring function must be disabled Information for the select...

Страница 5: ...or The safety outputs enable and allow a restart An interlocking chain must be permanently locked to enable the reactivation If more than one fault is detected at the safety outputs or a cross circuit is detected between Y1 and Y2 the solenoid interlock will be electronically locked and a normal fault reset will no longer be possible To reset this type of interlocking the solenoid interlock must b...

Страница 6: ...id interlocks can be wired in series For the evaluation of the serial diagnostics line either the PROFIBUS Gateway SD I DP V0 2 or the Universal Gateway SD I U are used This serial diagnostic interface is integrated as a slave in an existing field bus system In this way the diagnostic signals can be evaluated by means of a PLC The response data and the diagnostic data are automatically and permane...

Страница 7: ...it 1 7 Set up and maintenance 7 1 Functional testing The safety function of the safety components must be tested The following conditions must be previously checked and met 1 Fitting of the solenoid interlock and the actuator 2 Check the integrity of the cable entry and connections 3 Check the switch enclosure for damage 7 2 Maintenance We recommend a regular visual inspection and functional test ...

Страница 8: ...ge must be removed from all components up to the last component The voltage is supplied at both safety inputs of the terminal safety component of the chain considered from the safety monitoring module The safety outputs of the first safety component are wired to the safety monitoring module X1 Y1 X2 Y2 1 2 3 5 6 8 X1 X2 24V GND Y1 Y2 1 2 3 5 6 8 X1 4 Y1 4 Y1 X2 7 Y2 7 Y2 OUT 24V GND OUT SPS PLC IN...

Страница 9: ... IN Solenoid control SD input 8 4 RD OR without function 9 6 Connector plug ST1 M23 8 1 pole Connector plug ST2 M12 8 pole 1 2 9 3 4 5 6 7 8 5 8 4 3 2 1 7 6 Connecting cables with coupling female IP67 M23 8 1 pole 8 x 0 75 mm Connecting cables with coupling female IP67 IP69 M12 8 pole 8 x 0 23 mm to DIN 47100 Cable length Part number Cable length Part number 5 0 m 10 0 m 101209959 101209958 2 5 m ...

Страница 10: ...onform to the applicable European Directives Name of the component AZM 200 Type See ordering code Description of the component Interlocking device with electromagnetic inter lock for safety functions Relevant Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2004 AC 2005 A1 2009 EN 60947 5 3 2013 ISO 14119 2013 EN ISO 13849 ...

Отзывы: