background image

4

Operating instructions

Solenoid interlock

AZM 200 AS

EN

3.2  Manual release

For the machine set-up, the solenoid interlock can be unlocked in a de-

energised condition. After opening of the plastic flap "A" (refer to image 

"Dimensions"), the triangular key must be turned clockwise to bring 

the blocking bolt in unlocking condition. The normal locking function is 

only restored after the triangular key has been returned to its original 

position. Caution: do not turn beyond the latching point! After being 

put into operation, the manual release must be secured by closing the 

plastic flap "A" and affixing the seal, which is included in delivery.

Component ready for operation

Component not ready for operation

3.3  Dimensions

All measurements in mm.

40

220

155,5

5

6,5

32,5

7,5

20 1

±

50

24,4

M12

A

Key

A: Manual release under plastic cover

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition. 

The AZM 200 AS solenoid interlock is supplied through the AS-

Interface system. The energy for the locking magnet is individually 

supplied (AUX). Both voltage supplies of the solenoid interlock must 

be equipped with a protection against permanent overvoltage. To that 

effect, stabilised PELV supply units must be used. The connection to 

the AS-Interface system is realised through an M12 connector. The M12 

x 1 connector has an A-coding. The wiring configuration of the M12 

connector is defined as follows (to EN 62026-2):

AUX +(P)

3

2

1

4

AS-Interface -

AS-Int

AUX -(P)

5.  Functions and configuration

5.1  Mode of operation of the safety outputs

AZM 200 ST-T-AS

The safety outputs of the AS-i safety monitor are enabled,  

when the following conditions are met:

• guard door detected

• the actuator is inserted

• the solenoid interlock is locked

AZM 200 B ST-T-AS

The safety outputs of the AS-i safety monitor are enabled,  

when the following conditions are met:

• guard door detected

• the actuator is inserted

AZM 200 BZ ST-T-AS

The safety outputs of the AS-i safety monitor are only activated,  

when both AS-i half-codes are enabled.

Half-code 1

 (AS-i SaW bit 0,1) is enabled, when:

• guard door detected

• the actuator is inserted

The solenoid interlock now can be locked!

Half-code 2 

(AS-i SaW bit 2,3) is enabled, when:

• the solenoid interlock is additionally locked.

5.2  Magnet control

The control system with the AS-Interface Master can lock and unlock 

the solenoid interlock through the output bit 0 of the addressed AS-i 

slave AZM 200 AS. In the power to lock variant of the AZM 200 AS, 

the functional set of output bit 0 will cause the solenoid interlock to be 

locked. In the power to unlock variant of the AZM 200 AS, the functional 

set of output bit 0 will cause the solenoid interlock to be unlocked.

5.3  Programming the slave address

The slave address is programmed through the M12 connector.  

Any address from 1 to 31 can be set by means of the AS-i bus master 

or a hand-held programming device.

5.4  Configuration of the safety monitor

The AZM 200 AS can be configured in the ASIMON configuration 

software with the following monitoring devices (also refer to the 

ASIMON manual).

Double channel dependent

Suitable for: AZM 200 ST-T-AS, AZM 200 B ST-T-AS,  

AZM 200 BZ ST-T-AS

•  Synchronisation time typically: 0.1 s;  

for AZM 200 BZ ST-T-AS infinite (∞)

• Optionally with startup test

• Optional with local acknowledge

When the AZM 200 BZ ST-T-AS is used together with this monitoring 

device for conducting the start-up test prior to every restart, the safety 

guard must be opened.

Double channel conditionally dependent

Suitable for: AZM 200 BZ ST-T-AS

• Independent: In-1

As long as the actuator remains inserted, the safety guard can be 

relocked at any time, in which case the safety outputs are reactivated. 

The safety guard must not be opened.

The configuration of the safety monitor must be tested and 

confirmed by a qualified and authorised safety expert/safety 

engineer.

Содержание AZM 200 AS

Страница 1: ...the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions...

Страница 2: ...is a safety switch with an interlock function for process protection The safety function consists of safely switching off the code transfer when the guard system is unlocked or opened and maintaining...

Страница 3: ...rin ciple of isolating the supply of power to the solenoid The safety classification for the release function only applies to devices with monitored interlock function in power to unlock version and w...

Страница 4: ...uts of the AS i safety monitor are enabled when the following conditions are met guard door detected the actuator is inserted AZM 200 BZ ST T AS The safety outputs of the AS i safety monitor are only...

Страница 5: ...cyclically queried by the control system through the AS i master To that effect the 4 input bits with the varying SaW code of a Safety at Work slave are evaluated through an OR operation with 4 inputs...

Страница 6: ...be observed refer to error warning switch off after 30 min 7 Set up and maintenance 7 1 Functional testing The safety function of the safety components must be tested The following conditions must be...

Страница 7: ...2013 Notified body for the prototype test T V Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5122 01 15 Person authorised for the compilatio...

Страница 8: ...K A Schmersal GmbH Co KG M ddinghofe 30 42279 Wuppertal Germany Phone 49 202 6474 0 Telefax 49 202 6474 100 E Mail info schmersal com Internet www schmersal com...

Отзывы: