Electrical Connection and LED Display
5.6
5.6.1 Electrical Connection
The connection for control of the solenoid valve made using an 4-pole M12 connector that is integrat-
ed into the end cover. 24V DC ± 10%, max. power input: 2W, rated current: 0.1 A.
Standard = PNP switching.
The plug connectors must not be connected or disconnected when the system is live.
The power supply and signal inputs have a maximum line length of 30 meters.
DANGER
Inappropriate voltage supply
Electric shock, destruction of the electrical components
►
Connection work may only be carried out by a qualified electrical specialist.
► The system must incorporate safe electrical cut-off of the power supply in com-
pliance with EN60204
► Do not connect or disconnect the plug connectors when voltage is applied.
► Only operate the system with protected extra-low voltage.
Observe the separate operating instructions when connecting the vacuum genera-
tor.
Plug
Pin
Lead color
Function (PNP)
1
Brown
Not used
2
White
“Blow off ON” signal input (= deposit work-
pieces)
3
Blue
Ground
4
Black
“Extend cylinder ON” signal input
(= close and charge the vacuum reservoir)
ATTENTION
Incorrectly connected screw union
Malfunction
►
The multi-
pole plug’s screw union must be sealed securely and correct-
ly during installation of the customer’s cable.
1
2
3
4