background image

*P516-871*

P516-871

L-Series Electrified Lock

All installations should be in accordance with local electrical codes and national electrical code, NFPA 70.

L909X/L949X-Series and 

LM929X-Series electrified 

locks offer selection between 

one of two modes, EL or EU.
Select the appropriate mode 

for the installation using the 

mode select switch located

 

on the mortise chassis.

EL, electrically locked 

(fail safe):

Outside knob/lever or both 

outside and inside knobs/

levers (depending on 

function) will lock when 

power is applied. In the 

event of power failure, the 

opening will be unlocked.

EU, electrically unlocked 

(fail secure):

Outside knob/lever or both 

outside and inside knobs/

levers (depending on 

function) will unlock when 

power is applied. In the event 

of power failure, the opening 

will be locked.

Note: When mode is switched (from EL to EU or EU to EL) the lock requires a complete lock/unlock power cycle to synchronize to 

the proper mode.

IMPORTANT! Connection of L-Series electrified mortise locks to a supply circuit containing electromagnetic devices (i.e., solenoid based) 

is not 

recommended

. If used, the resulting transient voltages could damage the lock. The transient voltage must be carefully suppressed at the equipment 

producing it before connecting the lock to the same circuit. A varistor rated at 35 V (peak recurrent) may be used for transient voltage protection.

 WARNING

L9091/93/95, L9493/95 and LM9291/93/95 functions lock both inside and outside levers. Locking both levers

 

will prevent normal egress from the inside and will prevent the intended operation of an emergency exit.

Lock installation conditions and UL statements (applies only to L909X/L949X-Series locks):

• 

The lock shall be installed so as not to interfere with the intended operation of panic hardware installed on the same door.

• 

The lock shall be installed with a handle and spindle that meet the requirements of the ULC-S319 torque test or that are designed to sheer and 

not cause damage to the lock at a torque less than 305 N-m.

• 

All interconnected equipment must be UL/ULC Listed.

• 

Lock to be powered by a power-limited class 2, UL 294/UL 603 and ULC-S318/ULC-S319 Listed power supply capable of supplying 12/24 VDC.

• 

External source for RX, DM, LX, and DPS shall be a UL Listed power source with Class 2, power-limited output.

• 

For ULC-S319 Class II, III and IV installations, the door must be provided with a door position switch.

• 

UL 294 Access Control Performance Levels: Destructive Attack, Level 1; Line Security, Level 1; Standby Power, Level 1; Endurance, Level IV 

(with  DM, or LX, Endurance, Level I).

• 

ULC-S319 Class III

Troubleshooting

If lock does not operate:

• 

Ensure the lock is powered with DC power. Do not use AC power.

• 

Ensure the input voltage is between 10.8 and 26.4 volts DC.

L-Series Electrified Locks

L909X/L949X-Series Electrified Mortise Lock,

 

LM929X-Series Electrified Two-Point Lock (not 

UL/ULC Listed)
Wiring Instructions and Specifications

 WARNING

Warnings indicate potentially hazardous conditions, which if not 

avoided or corrected, may cause death or serious injury.

WARNINGS

L909X/L949X

LM929X

Mode select

 

switch

Electrified hinge/

EPT (not furnished)

12 or 24 V DC

Switch

 

(not furnished)

Power supply

 

12 or 24 VDC

 

(not furnished)

Lock to hinge/EPT 

harness (not furnished)

Electrical Requirements:

The 

L909X/L949X

 and LM929X-Series 

electrified locks are powered by DC power only.

 

Do not use AC power.

• 

Voltage: 12 or 24 VDC (maximum 26.4 V, 

minimum 10.8 V)

• 

Peak current:

 

0.4 amps

• 

Holding current: 0.010 amps

• 

Operating temperature: 32°F to 120°F (0°C 

to 49°C)

• 

Maximum relative humidity 93%

Note: Either lock wire may be attached to either power 

supply terminal (+ or -).

 

AWG

14

16

18

20

Voltage

12 V

500'

 

(152 m)

300'

 

(91 m)

200'

 

(61 m)

100'

 

(30 m)

24 V

Up to 1000' (304 m)

Отзывы: