E X P L O S I O N P R O O F
on-off
3-pos
hazardous area
safe area
1
1
2
3
2 3
EXV-8230-P
230 VAC
EEx-e
1
3
2
4
1
2
3
5 6
PA
feedback-
potentiometer
PE
PE
L
N
205X9-01
PE
1
1
2
4
2 3
/2EE
EEx-e
1
3
2
PA
3
5
6
4 5 6
HS1
HS2
205X9-99
Aux. switch, potential free .../2EE
hazardous area
safe area
PE
1 2 3
EXV-824-P
EEx-e
4
4
5
6
5 6
PA
feedback-
potentiometer
1
2
3
24 VAC/DC
1
3
2
205X9-26
on-off
3-pos
hazardous area
safe area
PE
1
1
2
3
2 3
EXV-824
24 VAC/DC
EEx-e
1
3
2
4
4
PA
205X9-25
optional
heater
on-off
3-pos
hazardous area
safe area
PE
1
1
2
3
2 3
EXV-8230
230 VAC
EEx-e
1
3
2
4
4
PA
L
N
205X9-00
optional
heater
on-off
3-pos
hazardous area
safe area
subject to change
page 1 of 3
2
)
for steam valves:
do not mount in vertical position
w x h x d = 110 x 75 x 57 mm
2..4 x M20x1,5
EXV-...-P
EXV-...-Y
EXV-.../2EE
w x h x d = 70 x 70 X 45 mm
3 x M20x1,5
EXV-..230
EXV-....24
2
)
ø 130
135
210
1
)
B
A
Meassures A and B in dependance of valve type
1
)
for continuous actuators 233 mm
perpendicular
3
)
Mounting position
EEx e terminal box
EXV-8...
Valve actuators for control valve bodies or on-off function. Explosionproofed in acc. with
"flameproof enclosure" and dust ignition proof, PTB tested. Installation in hazardous areas zone 1, 2,
21, 22. The actuators are 100% overload protected and can be stopped in any position. The controller
must be stable and should not pulse. Application: For industrial plant. For
Offshore
applications we
recommend the special types
EXV-8.../CT and EXV-8.../VA.
Valve actuator
800 N
Type
EXV-8230
EXV-8230-P
EXV-8230-Y
EXV-8230-Y/I
Supply voltage ± 10%
230 V/50 Hz
230 V/50 Hz
230 V/50 Hz
230 V/50 Hz
Type
EXV- 824
EXV- 824-P
EXV- 824-Y
EXV- 824-Y/I
Supply voltage
± 10%
24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
Power consump. motor
~11 VA
~11 VA
~11 VA
~11 VA
Starting current
capacitive load
capacitive load
capacitive load
capacitive load
I
START
>> I
TYP
I
START
>> I
TYP
I
START
>> I
TYP
I
START
>> I
TYP
Force
³
800 N
³
800 N
³
800 N
³
800 N
Running time
~6 sec/mm
~6 sec/mm
~6 sec/mm
~6 sec/mm
Stroke, in dep. of type
10 - 40 mm
10 - 40 mm
10 - 40 mm
10 - 40 mm
Control mode
on-off
on-off
2... 10 V
4... 20 mA
3 pos
3 pos
Input resistance
80 K
W
(~0,2 mA) 500
W
Feedback signal
-
1000
W
2... 10 V
2... 10 V
Endswitches
no endswitches, actuators are overload protected
Ambient temperature
0... 40 °C, non-condensing
Housing material
Aluminium baked varnish
Rod material
1.4034
Weight
~6 kg
Indication
CE Nr. 0158
Permission
PTB-tested acc. to directive 94/9/EC (ATEX)
Certificate
PTB 99 ATEX 1103
Explosionproof
II2G EEx d IIC T6, CENELEC EN 50014/ EN 50018
II2D IP65 T95°C, CENELEC EN50281-1-1
External PE-connector
Connectable lines: 4 mm
2
multiple-wire, 6 mm
2
single-wire
Prot. in acc. with EN 60529
IP 65
Operating mode
S3 80%ED acc. to EN60034-1 minimum run time of the actuator >1 sec.
Included
Actuator with 0.3m cable and protection tube, II2G/D EEx e terminal box
with mounting bracket
Installation area
hazardous areas zone 1, 2, 21, 22
/K
Heater for outdoor application and/or at high
humidity for reducing water condensation.
Power consumption of the heater ~16 W.
/CT
All housing parts aluminium with
Amercoat
v a r n i s h f o r
O f f s h o r e
a p p l i c a t i o n s .
/VA
All housing parts in
stainless steel
A I S I 3 1 6
f o r
O f f s h o r e
a p p l i c a t i o n .
/2EE
2 integral, potential free aux. switches,
switching in end-positions.
/HV
Emergency manual operation.
Adaptors
different types for different valve bodies.
EXC-HSV
2 external aux. switches, potential free
contacts, each adjustable.
EXC-K/HSV
EEx-Terminal box for EXC-HSV.
MOL-NG 24
Battery power pack, standby unit, 24V.
MOL-EH1
Electronic aux. switch, connectable to actuators
type EXV-...-Y, panel mounting.
/L16
Special Type with running time ~16 sec/mm.
The cable of the actuator must be installed in a fixed position
and protected against mechanical damage.
For installation, use and maintenance the official standards
and rules must be applied.
3) With horizontal installation position of the actuator, the
two spacer rods must form a vertical level.
Temperature class T6 is only for the actuator, you have to
guarantee max. temperature of valves and tubes on site.
The EEx actuators may only be opened by the
manufacturer to guarantee explosionproof and for
warranty.
For outdoor installation a heater and a weather protective
housing against rain, snow and sun is required.
After installation all componetes must fulfil the protection class
IP65 acc. EN60529.
2003/05/22
SCHISCHEK GMBH
D-90579 Langenzenn Mühlsteig 45 Gewerbegebiet V Tel.+49(0)9101-90810 Fax +49(0)9101-908177
e-mail:[email protected] Internet:http://www.schischek.com
II2G EEx d IIC T6
Zone 1, 2
II2D IP65 T95°C
Zone 21, 22
Electrical, explosionproof valve actuators
Type EXV-8...
List 3.0
for hazardous areas zones 1, 2, 21, 22 force 800 N - tested acc. to ATEX
APPLICATION
TECHNICAL DATA
ACCESSORIES
ELECTRICAL CONNECTION
DIMENSIONS
ATTENTION
Attention:
Voltage at terminal 2: rod is extending.
For continuous actuators see reverse.