Schischek EXV-8 Series Скачать руководство пользователя страница 1

E X P L O S I O N P R O O F

on-off

3-pos

hazardous area

safe area

1

1

2

3

2 3

EXV-8230-P

230 VAC

EEx-e

1

3

2

4

1

2

3

5 6

PA

feedback-

potentiometer

PE

PE

L

N

205X9-01

PE

1

1

2

4

2 3

/2EE

EEx-e

1

3

2

PA

3

5

6

4 5 6

HS1

HS2

205X9-99

Aux. switch, potential free .../2EE

hazardous area

safe area

PE

1 2 3

EXV-824-P

EEx-e

4

4

5

6

5 6

PA

feedback-

potentiometer

1

2

3

24 VAC/DC

1

3

2

205X9-26

on-off

3-pos

hazardous area

safe area

PE

1

1

2

3

2 3

EXV-824

24 VAC/DC

EEx-e

1

3

2

4

4

PA

205X9-25

optional

heater

on-off

3-pos

hazardous area

safe area

PE

1

1

2

3

2 3

EXV-8230

230 VAC

EEx-e

1

3

2

4

4

PA

L

N

205X9-00

optional

heater

on-off

3-pos

hazardous area

safe area

subject to change

page 1 of 3

2

)

for steam valves:

   do not mount in vertical position

w x h x d = 110 x 75 x 57 mm

2..4 x M20x1,5

EXV-...-P

EXV-...-Y

EXV-.../2EE

w x h x d = 70 x 70 X 45 mm

3 x M20x1,5

EXV-..230

EXV-....24

2

)

ø 130

135

210 

1

)

B

A

Meassures A and B in dependance of valve type

1

for continuous actuators 233 mm

perpendicular

 

3

)

Mounting position

EEx e terminal box

EXV-8... 

Valve actuators for control valve bodies or on-off function. Explosionproofed in acc. with

"flameproof enclosure" and dust ignition proof, PTB tested. Installation in hazardous areas zone 1, 2,

21, 22. The actuators are 100% overload protected and can be stopped in any position. The controller

must be stable and should not pulse. Application: For industrial plant. For 

Offshore

 applications we

recommend the special types 

EXV-8.../CT and EXV-8.../VA.

Valve actuator

800 N

Type

EXV-8230

EXV-8230-P

EXV-8230-Y

EXV-8230-Y/I

Supply voltage ± 10%

230 V/50 Hz

230 V/50 Hz

230 V/50 Hz

230 V/50 Hz

Type

EXV-  824

EXV-  824-P

EXV-  824-Y

EXV-  824-Y/I

Supply voltage

 

± 10%

24 VAC/DC 

24 VAC/DC

24 VAC/DC

24 VAC/DC

Power consump. motor

~11 VA

~11 VA

~11 VA

~11 VA

Starting current

capacitive load

capacitive load

capacitive load

capacitive load

I

START 

>> I

TYP

I

START 

>> I

TYP

I

START 

>> I

TYP

I

START 

>> I

TYP

Force

³ 

800 N

³ 

800 N

³ 

800 N

³ 

800 N

Running time

~6 sec/mm

~6 sec/mm

~6 sec/mm

~6 sec/mm

Stroke, in dep. of type

10 - 40 mm

10 - 40 mm

10 - 40 mm

10 - 40 mm

Control mode

on-off

on-off

2... 10 V

4... 20 mA

3 pos

3 pos

 

Input resistance

80 K

(~0,2 mA) 500 

W

Feedback signal

     -

1000 

W

2... 10 V

2... 10 V

Endswitches

no endswitches, actuators are overload protected

Ambient temperature

0... 40 °C, non-condensing

Housing material

Aluminium baked varnish

Rod material

1.4034

Weight

~6 kg

Indication

CE Nr. 0158

Permission

PTB-tested acc. to directive 94/9/EC (ATEX)

Certificate

PTB 99 ATEX 1103

Explosionproof

II2G EEx d IIC T6, CENELEC EN 50014/ EN 50018

II2D IP65 T95°C, CENELEC EN50281-1-1

External PE-connector

Connectable lines: 4 mm

multiple-wire, 6 mm

single-wire

Prot. in acc. with EN 60529

IP 65

Operating mode

S3 80%ED acc. to EN60034-1 minimum run time of the actuator >1 sec.

Included

Actuator with 0.3m cable and protection tube, II2G/D EEx e terminal box

with mounting bracket

Installation area

hazardous areas zone 1, 2, 21, 22

/K

Heater for outdoor application and/or at high

       

humidity  for  reducing  water  condensation.

 

Power consumption of the heater ~16 W.

/CT

All housing parts aluminium with 

Amercoat

 

v a r n i s h   f o r  

O f f s h o r e

  a p p l i c a t i o n s .

/VA

All  housing  parts  in 

stainless  steel

A I S I   3 1 6

  f o r  

O f f s h o r e

  a p p l i c a t i o n .

/2EE

2  integral,  potential  free  aux.  switches,

switching in end-positions.

/HV

Emergency manual operation.

Adaptors

different types for different valve bodies.

EXC-HSV

2  external  aux.  switches,  potential  free

contacts, each adjustable.

EXC-K/HSV

EEx-Terminal box for EXC-HSV.

MOL-NG 24

Battery  power  pack,  standby  unit,  24V.

MOL-EH1

Electronic aux. switch, connectable to actuators

type EXV-...-Y, panel mounting.

/L16

Special Type with running time ~16 sec/mm.

• The  cable of the actuator must be installed in a fixed position

and protected against mechanical damage.

•  For installation, use and maintenance the official standards

and rules must be applied.

• 3) With horizontal installation position of the actuator, the

    two spacer rods must form a vertical level.

• Temperature class T6 is only for the actuator, you have to

guarantee max. temperature of valves and tubes on site.

•  The  EEx  actuators  may  only  be  opened  by  the

manufacturer  to  guarantee  explosionproof  and  for

warranty.

• For outdoor installation a heater and  a weather protective

housing  against  rain,  snow  and  sun  is  required.

• After installation all componetes must fulfil the protection class

IP65 acc. EN60529.

2003/05/22

SCHISCHEK GMBH

• D-90579 Langenzenn • Mühlsteig 45 • Gewerbegebiet V • Tel.+49(0)9101-90810 • Fax +49(0)9101-908177

• e-mail:[email protected] • Internet:http://www.schischek.com

II2G EEx d IIC T6

Zone 1, 2

      II2D IP65 T95°C

Zone 21, 22

Electrical, explosionproof valve actuators

Type EXV-8...  

List 3.0

for hazardous areas zones 1, 2, 21, 22 – force 800 N - tested acc. to ATEX

APPLICATION

TECHNICAL DATA

ACCESSORIES

ELECTRICAL CONNECTION

DIMENSIONS

ATTENTION

Attention: 

•  Voltage at terminal 2: rod is extending.

•

 

For continuous actuators see reverse.