Parameter 0:
Position 0% is approached. The “Ready for operation” relay will be
switched in this case.
Parameter 1:
Drive stops at current position. The “Ready for operation” relay is
not
switched in this case.
Parameters 2-9:
Selected position 0% -
100% is approached in 8 steps. The “Ready
for operation” relay is
not
switched in this case.
Mode 5: Setting the speed
The rotation speed is selected:
Parameters 0-9:
Select the desired rotation speed in 10 steps according to the
“Settings”
table. The selected rotation speed is always related to a swivel range of
90°.
Mode 6: Setting the averaging
The duration of the averaging process for the analogue setpoint input is selected.
Higher durations will use more individual measurements for averaging. A higher setting
can counteract any fluctuations in the input signal level.
Parameters 0-9:
Selection of averaging in 10 steps from 0 s to 1.8 s.
Mode 7: Setting the ramp
Use this mode to select the duration of the start and hold ramps. In the three-point step
and manual modes, the drive is always stopped immediately when the end positions
are reached or when the move signal drops. The holding ramp is only used in control
mode.
Parameters 0-9:
Select the duration of the start and holding ramp in 10 steps from
0.05 s to 2.5 s.
Содержание 00-10/30 STEP
Страница 28: ...Connections by Antriebs Regeltechnik Schimpf GmbH 28 Figure 10 CPU board 00 15 Figure 11 Add on board 00 15 ...
Страница 69: ...Declaration of Conformity by Antriebs Regeltechnik Schimpf GmbH 69 Declaration of Conformity ...
Страница 71: ...Dimensional drawing by Antriebs Regeltechnik Schimpf GmbH 71 Figure 15 Dimensions of drive type 00 15 ...
Страница 72: ...Dimensional drawing by Antriebs Regeltechnik Schimpf GmbH 72 Figure 16 Dimensions of drive type 01 15 ...