SCHIEBEL LK Series Скачать руководство пользователя страница 1

Operation manual for linear units type LK
DS-ENGLISH-SCHUB-LK-V1.00-2020.03.23

SEC-DS-ENGLISH-SCHUB-LK-V1.00-2020.03.23

Operation manual for linear units type LK

1

General

Type LK linear units are offered in different variants, see Table 1. These are mounted together with electric
open/close or modulating actuators, of the series CM, on valves which require a linear positioning movement.
These linear units convert the torque output from the actuator into an axial force through a ball screw drive.
Not only is a higher control accuracy allowed, but also a longer lifetime is provided with the use of a ball screw
drive. The combination of actuator and linear unit, is based on the required thrust and the necessary stroke.

Type

Actuator

Output

flange

Stroke

Output

thread

Pitch

Factor

(

Nm

kN

)

Weight [kg]

LK50

CM03

G0/F10

50mm

M20x1,5

5mm/rev

1,06

12,3

LK100

CM03

G0/F10

100mm

M20x1,5

5mm/rev

1,06

15,0

LK120

CM06

G0/F10

120mm

M20x1,5

5mm/rev

1,06

19,2

CM06

G

1
2

/F14

120mm

M36x3,0

5mm/rev

1,06

23,6

Table 1:

Technical data linear units

2

Structure

Figure shows e.g. an CM03 actutator with mounted LK linear unit. The linear unit itself consists essentially of
a solid cast housing, a mounted spindle nut and a non-rotating spindle, see Figure 2. To prevent contamination
by dusty ambient air and to ensure the mechanical protection, the linear unit is completely sealed with O-rings
at the output.

Figure 1:

CM03-Actuator with mounted LK100 linear unit

1

Содержание LK Series

Страница 1: ...e combination of actuator and linear unit is based on the required thrust and the necessary stroke Type Actuator Output flange Stroke Output thread Pitch Factor Nm kN Weight kg LK50 CM03 G0 F10 50mm M20x1 5 5mm rev 1 06 12 3 LK100 CM03 G0 F10 100mm M20x1 5 5mm rev 1 06 15 0 LK120 CM06 G0 F10 120mm M20x1 5 5mm rev 1 06 19 2 CM06 G1 2 F14 120mm M36x3 0 5mm rev 1 06 23 6 Table 1 Technical data linear...

Страница 2: ...n manual for linear units type LK DS ENGLISH SCHUB LK V1 00 2020 03 23 Figure 2 shows the exploded drawing of the linear unit Figure 2 This image shows the exploded view of the linear unit The parts are listed in table 2 2 ...

Страница 3: ... two subsections the procedures for assembly and disassembly of linear units on valves are explained step by step 4 1 Security and assembly instructions The device may only be mounted and commissioned by qualified personnel Qualified personnel within the meaning of this operating manual are persons who are familiar with as sembly commissioning and operation of this product and have the required ap...

Страница 4: ...ween linear unit and valve 11 Use the handwheel to move the linear unit to a center position to prevent accidental damage to the valve during startup 4 3 Disassembly 1 If the valve is fully closed move the valve cone to about ten percent OPEN position 2 Loosen the screws between the output flange of the actuator and the linear unit and dismount the actua tor 3 Open the spindle coupling between the...

Страница 5: ...ubricant recommendation Lubricating grease DIN 51825 K P R 40 i e Water repellent complex grease based on Al soap with high resistance to acids and alkalis Ambient Temperature 40 bis 85 C Worked penetration 0 1 mm 310 340 Dripping point ca 260 C NLGI Class 1 acid free not or only slightly reactive with water 5 ...

Отзывы: