Extension Board for MODBUS on SMARTCON Control Unit
DS-ENGLISH-MODBUS-V2.01-2019.05.15

SEC-DS-GERMAN-MODBUS-RTU-V2.01-2019.05.15

Extension Board for MODBUS-RTU on SMARTCON Control Unit

1

General Information

For SCHIEBEL ACTUSMART or SMARTCON actuators the standardized fieldbus interface MODBUS-RTU is
available.
This interface is a product option represented in hardware on the device, thus making it beneficial to advertise
intended use upon ordering.
Although enabling MODBUS-RTU a posterior is possible, such upgrades should only be performed by autho-
rized SCHIEBEL engineers or specially trained personnel.

MODBUS-RTU determines technical and functional characteristics of the serial fieldbus system used to con-
nect distributed autonomous devices. MODBUS-RTU distinguishes Master- and Slave-Devices and has been
designed for data-transmission on field-level, hence, the communication of central control units - as SPS or PC
- with decentrale field-devices over a fast serial connection.
Communication functionality is standardized by the MODBUS Organization (modbus.org).

The

physical communication layer

is based on a RS-485 interface connected through a shielded twisted

two-wire cable.

SCHIEBEL Actuators ACTUSMART or SMARTCON are always slave devices.

Communication settings

The detection of the settings of the Modbus RTU communication is done automatically in the SCHIEBEL
MODBUS-RTU slave module during communication start-up.

The supported baud rates are:
4800 bps, 7200 bps, 9600 bps, 14400 bps, 19200 bps, 28800 bps,
38400 bps, 57600 bps, 76800 bps, 115200 bps

The byte frame has following bits:
1 start bit
8 data bits, LSB first
1 parity bit (even, odd or mark)
1 stop bit

If mark parity is not supported by the MODBUS-RTU master, you can use no parity and 2 stop bits instead.

2

Connection

Depedning on the order there are the following connections possible:

standard design: connection board

explosion proof design: terminals

2.1

Standard design

Connecting the actuator to the fieldbus system is accomplished through connecting the bus cable to the con-
nection print in the connection compartment of the actuator. Thus for convinience, the MODBUS-RTU con-
nector is pluggable like every other external connector for signal or power on our actuators. Disconnecting
a device will have no effect on the communication of other devices in the same strand. Meaning, the net-
work maintains full functionality if a device is disconnected while the network is in operation. But beware: At
the end of each strand MODBUS-RTU has to be terminated. This termination can either be performed by
a SMARTCON-Actuator or a separate active bus termination device. Note that the power for the termination
resistors of SMARTCON-Devices comes from the actuator. Hence, disconnecting the terminating SMARTCON

1

Содержание ACTUSMART

Страница 1: ...ion of the settings of the Modbus RTU communication is done automatically in the SCHIEBEL MODBUS RTU slave module during communication start up The supported baud rates are 4800 bps 7200 bps 9600 bps 14400 bps 19200 bps 28800 bps 38400 bps 57600 bps 76800 bps 115200 bps The byte frame has following bits 1 start bit 8 data bits LSB first 1 parity bit even odd or mark 1 stop bit If mark parity is no...

Страница 2: ...al channel version Option redundant is connected via channel I and II 2 1 1 Connection Board customer end The connection board is situated in the connection compartment under the topmost cover Figure 1 Connection Board 2 1 2 Connecting to MODBUS RTU Recommended Cable Confectioning Prior to connection the bus lines are to be confectioned as seen in the figure below The clamps on the connection boar...

Страница 3: ...ugh the termination resistor implemented in your SMARTCON Device Bus termination is activated when the re spective switch on the connection board is switched to ON as seen in figure 4 2 2 explosion proof design Normaly in explosion proof deisgn there is no termination available in the control unit That means that the bus termination must be done seperate outside of the control unit Optionaly also ...

Страница 4: ... Outputs Figure 6 1 shielding connection clamp 2 additional frame 3 metallic cable glands closed with blind screw connections at delivery 4 xM20x1 5 4 terminal strip 2 2 2 Design without bin In and Outputs Figure 7 1 shielding connection clamp 2 terminal strip An additional frame with 4xM20 holes is possible on special request 4 ...

Страница 5: ... 4 Modbus Watchdogtime 0 0 10 0s 0 0s Monitoring period of the togglebit Bit 7 in Master s command This bit has to toggle in the specified time or a buswatchdog error is detected If Watchdogtime is set to 0 0s the watchdog is deactiveted Toggling the respective bit can now be ommited P15 5 Modbus Setpoint Source 0 Standard Setpoint specified by MODBUS RTU effective only if positioner is activated ...

Страница 6: ...le Register Writes data to one single register in the slave 16 10 hex Preset Multiple Registers Writes data to multiple consecutively registers in the slave 03 03 hex Read Holding Register Reads back one single register from the slave 04 04 hex Read Input Register Reads back one single register from the slave 23 17 hex Read Write Multiple Registers Writes data to multiple consecutively registers i...

Страница 7: ...itioner in REMOTE mode 7 WATCHDOG Togglebit for buswatchdog Bit has to toggle before specified time out or a buswatchdog error will be detected 8 OPEN SH Latched OPEN in REMOTE mode Release with STOP 9 CLOSE SH Latched CLOSE in REMOTE mode Release with STOP 10 LOCK OPEN Locks OPEN in REMOTE and LOCAL mode Actuator carries out a latched OPEN command with highest priority which can only be released ...

Страница 8: ...Bit setting for intermediate position see table 2 page 8 11 Definition intermediate position Bit setting for intermediate position see table 2 page 8 12 PVST Start start PVST 13 reserved 14 reserved 15 reserved Bit11 Bit10 Bit9 Function 0 0 0 move to intermediate position Position 1 0 0 1 move to intermediate position Position 2 0 1 0 move to intermediate position Position 3 0 1 1 move to intermed...

Страница 9: ...ata format 16 bit Bitfield Bitno Function Description Bit 0 Bit 1 0 READY Actuator is ready 1 END POSITION OPEN End position OPEN reached under consideration of switch off mode torque or travel dependent 2 END POSITION CLOSE End position CLOSE reached under consideration switch off mode torque or travel dependent 3 TRAVEL OPEN End travel OPEN reached under consideration of switch off mode torque o...

Страница 10: ...oller Register number 261 address 0104Hex Data format 16 bit only the lowest 10 bits 0 1023 are in use Other bits are reserved for future use and have to be set to zero 4 2 6 Status 2 Register number 262 address 0105Hex Datenformat 16 bit Bitfield Structure Bitno Function Description Bit 0 Bit 0 1 0 Dig Output 1 Corresponding binary output enabled 1 Dig Output 2 2 Dig Output 3 3 Dig Output 4 4 Dig...

Страница 11: ...ster number 264 address 0107Hex Data format 16 bit Bitfield Structure Bitno Function Description 0 and 1 Channel activity Bit1 Bit0 Signal 0 0 Bus Channel A active 0 1 Bus Channel B active 1 0 Bus Channel A and B active main channel for inputs is channel A 1 1 Bus Channel A and B active main channel for inputs is channel B 2 reserved 3 reserved 4 reserved 5 reserved 6 reserved 7 reserved 8 and 9 P...

Отзывы: