Operation
P746/EN
OP/G31
MiCOM P746
(OP) 5-
17
OP
2.
ISOLATOR AND CIRCUIT BREAKER FUNCTION
2.1
Isolator State Monitoring Features
The following recommended functions, if used shall be set in the PSL:
MiCOM relays can be set to monitor normally open (89A) and normally closed (89B) auxiliary
contacts of the isolators. Under healthy conditions, these contacts will be in opposite states.
Should both sets of contacts be open, this would indicate one of the following conditions:
•
Auxiliary contacts / wiring defective
•
Isolator is defective
•
Isolator is in isolated position
Should both sets of contacts be closed, only one of the following two conditions would apply:
•
Auxiliary contacts / wiring defective
•
Isolator is defective
A normally open / normally closed output contact has to be assigned to this function via the
programmable scheme logic (PSL). The time delay is set to avoid unwanted operation during
normal switching duties. If any of the above conditions exist, an alarm will be issued after the
time delay set in the PSL.
In the PSL Qx must be used following the two options:
•
89A (normally open) (recommended) or 89B (normally closed) (not recommended)
•
Both 89A and 89B (recommended as long as the number of Input is sufficient)
If both 89A and 89B are used then status information will be available and in addition a
discrepancy alarm will be possible. 89A and 89B inputs are assigned to relay opto-isolated
inputs via the PSL.
2.2
Circuit Breaker State Monitoring Features
To monitor the CBs and isolators, the following recommended functions shall be set in the PSL.
MiCOM relays can be set to monitor normally open (52A) and normally closed (52B) auxiliary
contacts of the circuit breaker. Under healthy conditions, these contacts will be in opposite
states. Should both sets of contacts be open, this would indicate one of the following
conditions:
•
Auxiliary contacts / wiring defective
•
Circuit Breaker (CB) is defective
•
CB is in isolated position
Should both sets of contacts be closed, only one of the following two conditions would apply:
•
Auxiliary contacts / wiring defective
•
Circuit Breaker (CB) is defective
If any of the above conditions exist, an alarm will be issued after a 200ms time delay. A
normally open / normally closed output contact can be assigned to this function via the
programmable scheme logic (PSL). The time delay is set to avoid unwanted operation during
normal switching duties.
In the PSL CB AUX could be used or not, following these options:
•
None
•
Both 52A and 52B
(triphase - 2 optos)
•
Both 52A and 52B
(per phase - 6 optos)
Содержание MiCOM P746
Страница 4: ......
Страница 5: ...Pxxx EN SS G11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Страница 16: ...P746 EN IT G31 Introduction MiCOM P746...
Страница 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Страница 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Страница 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Страница 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Страница 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Страница 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Страница 114: ...P746 EN OP G31 Operation MiCOM P746...
Страница 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Страница 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Страница 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Страница 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Страница 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Страница 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Страница 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Страница 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Страница 280: ......
Страница 342: ...P746 EN CM F21 Commissioning and Maintenance CM 10 62 MiCOM P746 CM Commissioning Engineer Customer Witness Date Date...
Страница 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Страница 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Страница 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Страница 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Страница 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Страница 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Страница 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Страница 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Страница 438: ......
Страница 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Страница 465: ...Installation P746 EN IN G31 MiCOM P746 IN 15 27 IN 10P74611 1 FIGURE 18 MiCOM P746 80TE WIRING DESCRIPTION P746xxxL...
Страница 468: ......
Страница 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Страница 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Страница 502: ......
Страница 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Страница 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Страница 529: ......