Operation Manual VISATRON® VN115/87plus EX
06/2016
Page 24
SCHALLER AUTOMATION
D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG
Tel. +49(0)6842-508
-
0
/ Fax -260 / eMail: [email protected] / www.schaller.de
Shown is non-operated relay condition
Description
Pin
Description
24 Volts DC +
1
9
'Pre-alarm' relay
24 Volts DC GND
2
10
'Pre-alarm' relay
'Ready' relay closed
3
11
RS485 B (opt. 4 - 20 mA -)
'Ready' relay open
4
12
Reserved, do not use
'Ready' relay common
5
13
RS485 A (opt. 4 - 20 mA +)
'Alarm' 1 relay closed
6
14
'Alarm' 2 relay closed
'Alarm' 1 relay open
7
15
'Alarm' 2 relay open
'Alarm' 1 relay common
8
16
'Alarm' 2 relay common
Figure 19:
Pin assignment
-
We recommend connecting 'Alarm' 1 to the alarm system and 'Alarm' 2 to
the safety system.
-
Alarms 1 and 2 are getting switched simultaneously by same relay.
-
The relay outputs are potential-free.
-
In case of a High Oil Mist Alarm, contacts 7 and 8 as well as 15 and 16
are closing
-
In case detector goes into ‘READY’
-Mode, contacts 4 and 5 are closing
-
In case Pre-Alarm is activated, contacts 9 and 10 are opening. Pre-Alarm
will be switched as soon as 70% of High Oil Mist Alarm level is reached.
Power supply
18
–
31.2 Volts DC, max. 2 A
Nominal voltage
24 Volts DC
Relay Outputs
Max. 60 Volts DC, 1 A
Internal fuse
2 A semi time lag
Table 1:
Electrical specification