11. Electrical Connection

12. Controller Programming

The cooling unit is used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to 

protect heat sensitive components. The unit has two completely separate air circuits which ensure that the clean cabinet 

air does not come into contact with the ambient air which may well be dirty or polluted. Control cabinet air conditioners can 

dissipate large quantities of heat from sealed enclosures, such as control cabinets, into the ambient air and at the same time 

reduce the cabinet internal temperature to below that of the ambient air.

The control cabinet air conditioner can function without problems in extreme ambient conditions (e.g. dusty and oily air) 

with a standard operating temperature ranging between -4°F and 131°F. The stated cooling capacities are according to DIN 

3168.

Door Switch

The unit can be switched on and off via a door contact switch. When delivered the door contact terminals are bridged on the 

female connector. To connect the door contact switch remove the bridge and connect door contact switch. The contact must 

be closed when the cabinet door is closed.

SET

TEST

BMS

PRG

R
D

!

1

2

3

4

The cooling unit is intended to be used as a complementary accessory to larger industrial

equipment. The unit is used where heat needs to be dissipated from electrical control 

cabinets or similar enclosures in order to protect heat sensitive components. It is not 

intended for household use. The unit has two completely separate air circuits which 

ensure that the clean cabinet air does not come into contact with the ambient air which 

may well be dirty or polluted. Enclosure cooling units can dissipate large quantities of 

heat from sealed enclosures such as electrical enclosures into the ambient air and at 

the same time reduce the cabinet internal temperature to below that of the ambient air.

The  unit  can  function  without  problems  in  extreme  ambient  conditions  (e.g.  dusty 

and  oily  air)  with  a  standard  operating  temperature  ranging  between  +10°C  and 

+55°C.  Units  can  be  ordered  with  an  additional  electrical  cabinet  heater.  For  the 

cooling capacities and environmental ratings please refer to the type plate data.

The display shows the temperature in the range of -50°C to +150°C (-58°F to +302°F). The

temperature is displayed with resolution of tenths between -19.9°C and +99.9°C (-3.8°F 

to +211.8°F). During programming, it shows the codes and values of the parameters. The 

display also shows icons according to occurring events.

Controller

Содержание Enviro-Therm SCE-AC6800B460V3

Страница 1: ...ing p 7 8 Mounting Principle p 7 9 Cutout Dimensions p 8 10 Dimensions H x W x D p 8 11 Electrical Connection p 9 12 Controller Programming p 9 13 Wiring Diagram p 13 14 Taking Into Operation p 15 15...

Страница 2: ...ltage Indicates electric shock danger Important Safety Instruction Indicates instructions for safe maintenance and operation of the unit Attention Indicates possible burns from hot components Attentio...

Страница 3: ...y regulations One can find dangerous voltage above 50V AC or above 100V DC Behind the control cabinet doors On the power supply in the unit housing The units have to be fused according to the type pla...

Страница 4: ...ke and evaporator These four components of the refrigerant plant are connected with each other by pipes to form a hermetically sealed system in which the refrigerant R134a circulates 1 Air Intake Cabi...

Страница 5: ...eel Powder Coated SS Stainless Steel AISI 304 SS6 Stainless Steel AISI 316 Dimensions H x W x D 45 28 x 15 55 x 10 63 inch Weight 113 lbs Cutout Dimensions 12 40 x 10 40 inch 12 40 x 8 30 inch Rated O...

Страница 6: ...00B230V SCE AC6800B120V SCE AC6800B460V3 SCE AC6800B230VSS SCE AC6800B120VSS SCE AC6800B460V3SS SCE AC6800B230VSS6 SCE AC6800B120VSS6 SCE AC6800B460V3SS6 Enclosure Air Temp 131 F 55 C 122 F 50 C 95 F...

Страница 7: ...tering the cooling unit internal and external are not obstructed Cooling unit enclosure air suction hole must be installed at the highest possible point When installing the unit on a door ensure it ca...

Страница 8: ...ck to top 9 Cutout Dimensions 15 55 45 28 10 70 4 SLOPE 312 x10 98 10 83 10 83 10 83 10 83 98 15 55 13 98 12 40 1 57 10 43 59 3 94 8 27 21 06 45 28 MOUNTING PATTERN INTERNAL AIR OUTLET INTERNAL AIR IN...

Страница 9: ...d when the cabinet door is closed SET TEST BMS PRG R D 1 2 3 4 The cooling unit is intended to be used as a complementary accessory to larger industrial equipment The unit is used where heat needs to...

Страница 10: ...ss Flashes when activation is delayed or inhibited by protection times external disabling or other procedures in progress Flashes when alarms are active Signals operation of unit in heating mode Activ...

Страница 11: ...high temperature alarm threshold default 55 C 131 F 3 Press SET on the desired parameter to display the current value 4 Use or to reach the desired value 5 Pressing SET temporarily saves the new value...

Страница 12: ...no button is pressed for 10 seconds the display starts flashing and after 1 minute returns to the main display without saving changes l To increase scrolling speed press and hold the or button for at...

Страница 13: ...Motor Overload Protector AR Alarm Relay X4 Electrical Supply Connections 1 L1 380 415 400 460 V 50 60 Hz 3 2 L2 380 415 400 460 V 50 60 Hz 3 3 L3 380 415 400 460 V 50 60 Hz 3 4 Earth Ground 5 P1 High...

Страница 14: ...B 14 SAGINAW CONTROL ENGINEERING A C USER MANUAL back to top...

Страница 15: ...ing temperature St Verify values of parameter St Door switch contact is open Verify door switch Controller does not work Replace controller Internal fan works external fan and compressor do not work D...

Страница 16: ...shers 1 x Female Connector with shorted wired positions for door contact Saginaw Control and Engineering 95 Midland Road Saginaw MI 48638 5770 Phone 989 799 6871 Fax 989 799 4524 sce saginawcontrol co...

Страница 17: ...ot exceed minimum and maximum rated temperatures Must not exceed BTU Hr rating Filters must be cleaned regularly Must be installed and grounded in accordance with all relevant electrical and safety co...

Отзывы: