SAGINAW CONTROL & ENGINEERING  •  A/C USER MANUAL

back to top

14. Taking Into Operation

15. Repair

Attention!

The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately lubricated, the oil, which has 

been displaced during transport, must be allowed to flow back into it. The unit must therefore be allowed to stand for at 

least 30 minutes before being connected to the mains and taken into operation. Upon connection the internal fan will start 

working. If the temperature inside the enclosure is higher than the set value of the controller, both the compressor and 

external air fan start working. Once the air inside the enclosure reaches the set temperature, the compressor and external 

fan will stop.

The unit is pre-set at 95°F, which is suitable for most of the electronic devices.
If Drainage required, use PVC 10mm (3/8 inch) ID Hose.

Failure

Condition

Cause

Solution

Unit Does

Not Cool

Internal fan does not work

Power not connected.

Verify power supply

Internal fan works, external fan 

and compressor do not work

Enclosure temperature is 

below setting temperature (St)

Verify values of parameter "St"

Door switch contact is open

Verify door switch

Controller does not work

Replace controller

Internal fan works, external 

fan and compressor do not 

work Display shows alternating 

"OFF" and temperature

The sequence of the phases 

inside the power supply 

connector is incorrect

Change phases inside power 

supply connector

External and internal fan work, 

compressor does not work

Compressor motor electrical 

failure

Verify external fan, verify 

ambient temperature, clean 

condenser

Capacitor for compressor failed Replace capacitor

Compressor works, external 

fan does not work 

External fan needs to be 

replaced

Replace external fan

Enclosure 

Overheating

Compressor and fans (external 

and internal) work all the time

Unit cooling undersized

Enclosure needs a bigger 

cooling unit

Enclosure needs a bigger 

cooling unit

Thermal compressor protector 

triggered

Verify ambient temperature, 

clean condenser

Refrigerant leakage

Contact dealer/service center

Excessive 

Condensate

Door enclosure open

Ambient air gets into the 

enclosure

Ensure door is closed, add a 

door switch and connect it to 

controller

Door enclosure closed

Enclosure IP degree minimum 

IP54

Seal openings on enclosure

Damaged/misplaced sealing 

strip

Repair strip accordingly

Содержание Enviro-Therm SCE-AC10200B460V3

Страница 1: ...ng p 7 8 Mounting Principle p 7 9 Cutout Dimensions p 8 10 Dimensions H x W x D p 8 11 Electrical Connection p 9 12 Controller Programming p 9 13 Wiring Diagram p 13 14 Taking Into Operation p 15 15 R...

Страница 2: ...ltage Indicates electric shock danger Important Safety Instruction Indicates instructions for safe maintenance and operation of the unit Attention Indicates possible burns from hot components Attentio...

Страница 3: ...y regulations One can find dangerous voltage above 50V AC or above 100V DC Behind the control cabinet doors On the power supply in the unit housing The units have to be fused according to the type pla...

Страница 4: ...ke and evaporator These four components of the refrigerant plant are connected with each other by pipes to form a hermetically sealed system in which the refrigerant R134a circulates 1 Air Intake Cabi...

Страница 5: ...Steel Powder Coated SS Stainless Steel AISI 304 SS6 Stainless Steel AISI 316 Dimensions H x W x D 61 02 x 18 00 x 13 98 inch Weight 176 lbs Cutout Dimensions 14 80 x 12 80 inch 14 80 x 13 20 inch Rate...

Страница 6: ...e C Cooling Capacity BTU SCE AC10200B230V SCE AC10200B460V3 SCE AC10200B230VSS SCE AC10200B460V3SS SCE AC10200B230VSS6 SCE AC10200B460V3SS6 Enclosure Air Temp 131 F 55 C 122 F 50 C 95 F 35 C 68 F 20 C...

Страница 7: ...tering the cooling unit internal and external are not obstructed Cooling unit enclosure air suction hole must be installed at the highest possible point When installing the unit on a door ensure it ca...

Страница 8: ...op 9 Cutout Dimensions 17 99 14 02 61 02 61 02 17 99 1 97 12 80 12 01 13 19 21 06 14 84 8 07 8 07 93 98 98 1 58 16 14 13 19 11 22 14 57 14 17 6 89 312 x11 MOUNTING PATTERN INTERNAL AIR OUTLET INTERNAL...

Страница 9: ...t must be closed when the cabinet door is closed The cooling unit is intended to be used as a complementary accessory to larger industrial equipment The unit is used where heat needs to be dissipated...

Страница 10: ...ss Flashes when activation is delayed or inhibited by protection times external disabling or other procedures in progress Flashes when alarms are active Signals operation of unit in heating mode Activ...

Страница 11: ...high temperature alarm threshold default 55 C 131 F 3 Press SET on the desired parameter to display the current value 4 Use or to reach the desired value 5 Pressing SET temporarily saves the new value...

Страница 12: ...no button is pressed for 10 seconds the display starts flashing and after 1 minute returns to the main display without saving changes l To increase scrolling speed press and hold the or button for at...

Страница 13: ...Motor Overload Protector AR Alarm Relay X4 Electrical Supply Connections 1 L1 380 415 400 460 V 50 60 Hz 3 2 L2 380 415 400 460 V 50 60 Hz 3 3 L3 380 415 400 460 V 50 60 Hz 3 4 Earth Ground 5 P1 High...

Страница 14: ...B 14 SAGINAW CONTROL ENGINEERING A C USER MANUAL back to top...

Страница 15: ...ing temperature St Verify values of parameter St Door switch contact is open Verify door switch Controller does not work Replace controller Internal fan works external fan and compressor do not work D...

Страница 16: ...shers 1 x Female Connector with shorted wired positions for door contact Saginaw Control and Engineering 95 Midland Road Saginaw MI 48638 5770 Phone 989 799 6871 Fax 989 799 4524 sce saginawcontrol co...

Страница 17: ...ot exceed minimum and maximum rated temperatures Must not exceed BTU Hr rating Filters must be cleaned regularly Must be installed and grounded in accordance with all relevant electrical and safety co...

Отзывы: