User manual SCAIME:
NU-Soft-eNod4F-E-0716_235704-C.doc
bits
meaning
note
0110
Cycle in progress
In loss in weight feeder mode
0111
External totalizer
In loss in weight feeder mode
1000
Flowrate alarm
In loss in weight feeder mode
1001
Batch complete
In loss in weight feeder mode
1010
Refilling in progress
In loss in weight feeder mode
1011
Extraction activated
In loss in weight feeder mode
1100
Volumetric phase
In loss in weight feeder mode
b12
(or b4 in CANopen®)
output 2 logical
0
negative logic
defines the output level when enabled
1
positive logic
defines the output level when enabled
13.2.6
Logical outputs 3&4 assignment
Similar to the outputs 1&2 configuration parameter, see previous paragraph (replacing all references to output 1 by
output 3 and all references to output 2 by output 4).
13.2.7
Weight quantity per pulse on logical output
When a logical output is assigned to
external totalizer
, a pulse is generated every time the totalization increases a
multiple of a
weight quantity per pulse on logical output
. The maximum pulse frequency is 10 Hz and pulse duration
is fixed at 50ms. The output pulse is not rounded (i.e. the pulse is issued only once
weight quantity per pulse on
logical output
is strictly exceeded).