18
7
NEPTUNE PROTOCOL METER SUPPORT
The Neptune Protocol, as implemented within the E-
Coder™, ProCoder™, Mach10, and ProRead
line of registers, is fully supported by the EtherMeter.
Important Notes:
(1) See the Meter Compatibility Matrix for meter register configuration details.
(2) Wire color-coding for Neptune-compatibles differs from that used in Sensus-compatibles and
K-Frame-compatibles.
Figure 7A. Neptune E-
Coder™ – Register Diagram.
TERMINATION
DELIMITER
START
DELIMITER
TOTALIZATION DATA
(DIGITS 1-6)
TOTALIZATION DATA
(DIGITS 7-8)
NEPTUNE PROTOCOL:
7 DATA BITS, 1 START BIT, 1 STOP BIT, EVEN PARITY, ASCII ENCODING
SAMPLE READ. TOTALIZATION = 00000158
<STX> 2 0 0 S W <ETB> 0 0 0 0 0 1 <ETB> 1 2 3 4 5 6 7 8 9 0 <ETB> h <ETB> 5 8 @ <ETB> 7 2 <ETX>
Figure 7B. Neptune
– Protocol Diagram Example (Total=”00000158”).
To connect a Neptune-Protocol Register to Meter Channel 1:
EtherMeter Terminal
Neptune-Compatible Wire Color
14
Black
15
Red
16
Green
To connect a Neptune-Protocol Register to Meter Channel 2:
EtherMeter Terminal
Neptune-Compatible Wire Color
17
Black
18
Red
19
Green
Содержание EtherMeter EM-100
Страница 2: ......
Страница 38: ...36 Setup Screen 2 of 8 Serial Port Setup Setup Screen 3 of 8 Networking Setup...
Страница 39: ...37 Setup Screen 4 of 8 Auxiliary I O Setup Setup Screen 5 of 8 Interface Setup...
Страница 41: ...39 Setup Screen 8 of 8 Meter Read Diagnostics...
Страница 79: ...This Page Intentionally Blank...