INSTRUCTION MANUAL 

CHEMTROL® 

C

OMMERCIAL WATER 

CHEMISTRY 

CONTROLLERS 

MODEL ____________________ 

S/N________________________

 

WARRANTY 

This CHEMTROL® Controller is warranted by SANTA BARBARA CONTROL SYSTEMS (SBCS) to be free from defects in 
manufacturing and workmanship for a period of FIVE (5) YEARS from the date of purchase for the printed circuit boards and ONE (1) 
YEAR for all other components. SBCS will repair or replace at its option any defective part during the warranty period.  Labor, shipping 
or incidental expenses are specifically excluded from this warranty.  For warranty coverage, defective parts should be returned 
immediately  to  your  CHEMTROL® Dealer  or  to  our  factory  postpaid  with  a  copy  of  your  purchase  receipt  and  a  description  of  the 
malfunction. 

TECHNICAL SUPPORT 

800-621-2279
805-683-8833

US/CANADA 
OTHER COUNTRIES 

AUSTRALIA

EMAIL 

1

-3

0

0-585-820

support@

chemtrol

.com

.au

 

Содержание CHEMTROL CT Series

Страница 1: ...for the printed circuit boards and ONE 1 YEAR for all other components SBCS will repair or replace at its option any defective part during the warranty period Labor shipping or incidental expenses are...

Страница 2: ...und fault circuit interrupter GFCI The GFCI must be tested before each use With the product operating open the service door If the product stops operating this merely indicates that the door is equipp...

Страница 3: ...or Cables 21 Electrical Interference 21 Storage and Winterizing 22 Sensor Warranty 22 TEMPERATURE SENSOR 23 CONDUCTIVITY SENSOR 22 ELECTRONIC FLOW SENSOR 22 Hall effect sensor 22 Reed switch sensor 22...

Страница 4: ...8 3 ORP Booster 52 CHAPTER III COMMUNICATIONS 53 COMMUNICATION OPTIONS 53 REMOTE OPERATION OPTIONS 53 Direct Connection 53 Modem Connection Computer Software Installation 53 CHEMCOMTM Program 53 Autom...

Страница 5: ...water treatment is protection of the equipment from the aggressiveness of water and prevention of bacteriological growth The guidelines for Commercial water chemistry controllers include the followin...

Страница 6: ...rs biocides descalers etc with choice of feed programs manual automatic bleed feed or bleed then feed cycle timer percent of flow daily schedule or 2 week schedule controls with bleed and feed lockout...

Страница 7: ...running no Line 3 shows an ORP reading of 750 mV with the feed pump in the OFF mode X Line 4 shows a Temperature reading of 72 F Line 5 shows the Flow Rates for make up fill and bleed waters at 15 an...

Страница 8: ...page there are several Main Menus that are accessed directly from the Display Screen one for each operating function and one for system configuration The Submenus are additional menus that are accesse...

Страница 9: ...utomatic Timer of Flow Daily Schedule 2 Week Schedule BLEED AND FEED Feed Max Time Daily Schedule BLEED LOCKOUT Lockout Lock memory Pre bleed Pre bleed Pre pH DAILY SCHEDULE Next date Cycle days Start...

Страница 10: ...mplete monitoring and control of all water treatment operations including chemistry and filtration All information provided by the sensors is processed by the microprocessor on the Mother Board and di...

Страница 11: ...MANUAL CT Controllers INSTALLATION Page 11 Figure 2 CT6000 Schematic of Installation...

Страница 12: ...MANUAL CT Controllers INSTALLATION Page 12 Figure 3 CT6000 Controller Cabinet Figure 4 CT3000 Controller Cabinet...

Страница 13: ...ter flow in the recirculation line Panel Interlock For safety of operation a panel interlock switch is mounted inside the cabinet to shut off all internal power when the control panel is open DO NOT A...

Страница 14: ...er JP7 which is just below the power transformer Figure 6 CT3000 6000 Motherboard Notes 1 Contrast Adjustment is made with the contrast potentiometer R95 2 The terminal strips along the bottom edge ar...

Страница 15: ...e three position jumper JP7 which is just below the power transformer Notes 1 Display contrast adjustment is made with contrast adjustment potentiometer R85 2 uSd Card Socket is found along the bottom...

Страница 16: ...xpansion Slots In all of the Chemtrol CT Controllers there are five exp ansion slots available to add functional capabilities The capabilities that can be added include but are not limited to PPM Sani...

Страница 17: ...r 230V depending on the setting of the input voltage selector switch see preceding page Connect the leads to the alarm to the Normally Open contacts NO1 and NO2 on the terminal strip located next to t...

Страница 18: ...the controller and the communication would be initiated Some facilites disourage this type of access into their network In these cases Chemtrol can provide the Webserver access through a Cellular Mod...

Страница 19: ...cers Do not install the sensors near an elbow or a constriction where there might be excessive turbulence Install the tees on the suction side of the pump and make sure that the tip of the sensor is o...

Страница 20: ...solation valves on the bypass line and see the flow past the flow switch If there is no water flow replumb the bypass line as shown on the schematic NOTE The most common installation problems with byp...

Страница 21: ...n be used but it should not be overtightened The sensor with the upper part of the fitting should then be carefully inserted as shown on the schematic above being careful not to bend or overtighten it...

Страница 22: ...NIC FLOW SENSOR Either Hall effect type sensors or Reed switch Contacting Head type sensors can be used WARNING Follow all manufacturer s instructions carefully and do not install in line under pressu...

Страница 23: ...ed by NSF National Sanitation Foundation UL Underwriters Laboratories ETL Electrical Test Laboratories CSA Canadian Standards Association or similar national and international organizations can be use...

Страница 24: ...re used several filters can be banked together For filtration the valves are in the normally open position and connect the influent and effluent lines through each filter In backwash operation normall...

Страница 25: ...h standard defaults values for normal operating conditions On startup it uses the default values i e English language U S units no password standard setpoints and alarms etc The operator can change th...

Страница 26: ...3 Code Number The Code Number Submenu is used to define different operator access levels Code numbers may be required for access at key points in the program and for remote communications Up to ten fi...

Страница 27: ...stance an interval of 60 minutes one hour fills the memory in 41 days Data logging every four hours fills the memory in about 5 months To avoid losing test data remember to print it or download it to...

Страница 28: ...is not running in the bypass line may cause dangerous water conditions and hazardous chemical reactions 8 2 3 Langelier Saturation Index The Langelier Saturation Index is used for monitoring the devel...

Страница 29: ...efore recommended to download the data at periodic intervals to save it Downloading the data does not erase it from the memory chip To erase all data in memory use Submenu 8 1 6 Data Logging and selec...

Страница 30: ...ry settings This may be done on initial installation or whenever the operating parameters have been misadjusted by the operator Complete Reset resets all system parameters to their initial default set...

Страница 31: ...monitoring equipment BMS or control equipment pumps or valves with analog control circuitry The converter boards plug into separate areas of the mother board of the controller see Chapter II INSTALLAT...

Страница 32: ...ly Schedule S or 2 Week Schedule B To change the Control Mode select the first line with the UP or DOWN ARROW keys and press the RIGHT ARROW key The Control Mode screen is then displayed The Control M...

Страница 33: ...elect Scale The Select Scale prompt takes the operator to the SELECT SCALE Submenu 1 8 1 8 1 Cell Constant Conductivity is usually monitored with contacting type sensors which are made of two electrod...

Страница 34: ...our fields of information The first is the number of Cycles of Concentration that the unit is programmed for The second is the conductivity reading of the makeup water sensor The third is the units of...

Страница 35: ...Point calibration for origin slope and curvature This is done by pressing the RIGHT ARROW key to enter the CALIBRATION Submenu The calibration procedure is common to all control functions See CALIBRA...

Страница 36: ...After the cumulative run time is reset the TOTAL TIME ALARM submenu 3 7 1 is displayed to set the Total Time Alarm option It can be used to simulate a low chemical level alarm by entering the number...

Страница 37: ...th 1 2 or 3 Point calibration for origin slope and curvature This is done by pressing the RIGHT ARROW key to enter the CALIBRATION Submenu The calibration procedure is common to all control functions...

Страница 38: ...trol mode off and back on To reset the cumulative runtime enter zero in the last column After the cumulative run time is reset the TOTAL TIME ALARM submenu 3 7 1 is displayed to set the Total Time Ala...

Страница 39: ...dings The temperature sensor can be calibrated with 1 2 or 3 Point calibration for origin slope and curvature This is done by pressing the RIGHT ARROW key to enter the CALIBRATION Submenu The calibrat...

Страница 40: ...ed the influent pressure increases When the pressure gets too high it is necessary to remove the accumulated solid particles by backwashing With the CHEMTROL CT6000 this can done automatically by moni...

Страница 41: ...By pressing the RIGHT ARROW key the operator accesses the Fill Water History Submenu 5 3 Three counters are available for independent resets 5 4 Bleed Flow Rate Line 4 shows the bleed water flow rate...

Страница 42: ...by the manufacturer of the sensor The factory set default factors of 0 43 and 0 50 are valid for the transducer in the pressure range of 0 to 60 pi It should normally not require any adjustment 5 7 E...

Страница 43: ...the operator If nothing is selected the pump stays on all the time All scheduled times should be entered in the 24 00 hour format Different times can be entered for different days This allows for red...

Страница 44: ...5 sets the wait time between filters Line 6 6 sets the number of filters in the cycle up to 3 filters or banks of filters It then leads to Submenu 6 6 asking if a priority valve is used Line 6 7 calc...

Страница 45: ...9 psi or kg cm 2 6 1 3 Time and Pressure Differential This option causes a backwash cycle to be initiated when BOTH the specified interval number of days has passed AND the specified difference betwee...

Страница 46: ...r Percent of Flow and Daily Schedule are common to all control functions See CONTROL Submenu at the end of this Chapter for detailed explanations The AUTOMATIC control mode is different for Additives...

Страница 47: ...a malfunction of the chemical feeder 7 1 3 Run Time The RUN TIME displays the time in minutes for current activation and cumulative run time since last reset to zero To reset the cumulative run time...

Страница 48: ...to prevent overfeeding X Y 1 Deadband In all three automatic control modes ON OFF Proportional and 4 20 mA the controller uses a deadband zone near the setpoint to prevent chattering of the relay The...

Страница 49: ...return to the setpoint As the width of the Progressive Zone is decreased the reaction becomes faster and faster until eventually one approaches the conditions of ON OFF control X 1 3 3 4 20 mA Control...

Страница 50: ...chedule Control In the Daily Schedule Control mode the controller activates the control outlet for selected daily intervals regardless of sensor input Selection of the Daily Schedule control mode lead...

Страница 51: ...ered on the calibration screen as the new display value The controller uses the calibration value that has been entered by the operator to calculate the origin a of the representative linear equation...

Страница 52: ...level of shock treatment to reach in mV for Shock Treatment or in ppm or mg l for Superchlorination Chemical injection stops when either the set level is reached or the end time is reached 3 8 2 ORP D...

Страница 53: ...ged to the Windows Desktop screen using Windows Explorer To start the program click on the CHEMCOMTM icon CHEMCOMTM Program The main screen of the CHEMCOMTM program is shown on Figure 24 Menu 1 INSTRU...

Страница 54: ...wrates of 15 and 10 gpm respectively with the fill valve activated in the Automatic mode A Line 6 shows that the Filter Backwash is in Manual mode M with influent and effluent pressures of 25 and 20 p...

Страница 55: ...ta log can be displayed graphically with the CHEMCOMTM software program using Menu 8 for DISPLAY DATA and GRAPH As shown on Figure the graphics program displays two parameters simultaneously such as O...

Страница 56: ...he unit delivers the current status report As fu shown nction n above ame the status report includes current value applicable operating mode and applicable operational status The status report is repe...

Страница 57: ...l there is a smooth flow of water coming out of the tap no suction or excessive pressure Conductivity and Chemistry Adjustment Before starting automatic control the water chemistry should be adjusted...

Страница 58: ...RP deadband It will stop automatically as soon as the reading is above the ORP setpoint ADDITIVES Feed The CHEMTROL CT Controller has four 4 feed outlets for chemical additives such as inhibitors bioc...

Страница 59: ...igrating toward the junction shock the sensor with chlorine if stored over 3 months Battery Replacement The memory battery is located in the upper left corner of the Mother Board It keeps the configur...

Страница 60: ...pH meter consistently reads too low not enough soda the feed rate of the soda feed pump should be increased or a stronger solution should be used DO NOT CHANGE THE SETPOINT ORP Control To be sure of p...

Страница 61: ...f needed 3 If the PPM or pH readings are out of range a Investigate and correct the cause of the problem immediately b Readjust the water manually if needed and recalibrate the displays 4 If the displ...

Страница 62: ...bration of the pH probe The outputs of the ORP and pH simulators can be adjusted with the two small knobs located below the digital display The ORP range is 0 to 1 000 mV As shown in Table III the pH...

Страница 63: ...readings in millivolts as shown on the pH Scale Table Set the Mode Switch to TESTING Connect the pH sensor to the pH BNC connector on the tester Turn the Selector Knob to pH Place the pH sensor in nea...

Страница 64: ...OW or HIGH ALARM is flashing Adjust water chemistry manually Press RIGHT arrow to change alarm limits Set Feed Lockout to Off CAUTION 5c If RUN TIME line is flashing Increase chemical feeder rate Incr...

Страница 65: ...ic PC board for CT110 with microprocessor MB CT3000 MOTHER PC BOARD electronic PC board for CT3000 with microprocessor MB CT6000 MOTHER PC BOARD electronic PC board for CT6000 with microprocessor PB C...