Document 27-646; Version ENG01 │ 2015-08-27
Manual
Q.PS-PEL-240x
24 VDC Power Supply Unit
Страница 1: ...Document 27 646 Version ENG01 2015 08 27 Manual Q PS PEL 240x 24 VDC Power Supply Unit ...
Страница 2: ...s Document version Version Changes Published Remarks ENG01 2015 08 27 2015 08 27 New document Brands and trademarks Saia PCD and Saia PG5 are registered trademarks of Saia Burgess Controls AG Technical modifications are based on the current state of the art technology Saia Burgess Controls AG 2015 All rights reserved Published in Switzerland ...
Страница 3: ...unting packages all units feature overvoltage and short circuit protection Features Stabilised and adjustable output voltage Power output OK LED Parallel connection capability Spring loaded connector system DIN rail mounting Specifications Input Input rated voltage 100 to 240 Vac Input voltage range 85 to 264 Vac Input frequency range 44 to 66 Hz Inrush current limiter 30 A NTC Recommended 6A 10A ...
Страница 4: ...onductors Use Cu only rated 60 C or 60 75 C Installation Install in Pollution Degree 2 environment Feedback voltage max 30 Vdc Safety standards Safety EN61558 2 17 EN60950 SELV EMC EN61204 UL cURus cULus GL GL Germanischer Lloyd Indication Output power OK Green LED DC OK Input output terminals Connection technology Push in Conductor cross section single wire 0 2 2 5 mm2 Conductor cross section str...
Страница 5: ...C 2 8 A 55 C Efficiency 82 typ 88 typ Current rating at any mounting position Max 0 9 A Max 2 4 A Weight 0 17 kg 0 3 kg Dimensions 54 89 54 mm 90 89 54 mm Voltage Current Characteristic for short circuit and overload The output of the device is electrically protected against overload and short circuit Uout V Output Charac Iout A teristic U I Chara teristic c 1 1 IN N I Current overload protection ...
Страница 6: ...Manual Q PS PEL 240x 24 VDC Power Supply Unit Document 27 646 Version ENG01 2015 08 27 1 6 1 Dimensions Datasheet Dimensions H D1 D2 W Model Q PS PEL 2401 Q PS PEL 2403 W 54 mm 90 mm H 89 mm 89 mm D1 54 mm 54 mm D2 59 mm 59 mm ...
Страница 7: ...he adjustment screw anticlockwise reduces the voltage output VADJ Mount Dismount Mount unit by placing the DIN rail guide on the upper edge of the DIN rail and snapping it into place with a downward motion Dismount unit by levering the lower catch open with a screwdriver pulling the lower edge forward and unhooking from the top of the DIN rail Parallel connection If units have their outputs connec...
Страница 8: ...l accident prevention regulations e g UVV VBG4 or BGV A3 and the generally accepted rules of technology This equipment is a component designed for installation into electrical systems and machines and fulfils the requirements of the low volta ge guidelines 2014 35 EU The required minimum spacing to neighboring components must be observed to guaran tee the required cooling When installed into machi...
Страница 9: ...3280 Murten Switzerland Phone 41 26 580 30 00 Fax 41 26 580 34 99 Email support support saia pcd com Supportsite www sbc support com SBC site www saia pcd com International Represetatives www saia pcd com contact SBC Sales Companies Postal address for returns from customers of the Swiss Sales office Saia Burgess Controls AG Service Après Vente Bahnhofstrasse 18 3280 Murten Switzerland ...