PCD7.L452 Coupling Module 

 

Saia-Burgess Controls AG  

Bahnhofstrasse 18 

3280 Murten / Switzerland  

T+ 41 026 580 30 00 

www.saia-pcd.com 

 

 

 

 

899239 

26-044 ENG06   06-2016 

 

Describtion 

 

The analog data encoder PCD7.L452 is used as a regulating encoder for manual setting of 

manipulated variables e.g. for mixing valves, valve settings, temperatures etc. 

 

Function describtion 

 

The module offers three operation modes selectable by the three-position switch (ON, OFF, 

AUTO). The switch position is signaled by the external control contacts B1 and B2. 

 

Switch position “ON” 

The regulating variable is selected with the front-mounted potentiometer. The 0 to 10 V 

output signal is available at contact Y. 

 

Switch position “AUTO” 

The regulating variable is looped through without change to output Y via contact YR 

 

These coupling modules are provided with spring clamp terminal blocks allowing easy and 

quick wire termination. No tool is required to terminate solid wires and stranded wires with 

end sleeves. And to terminate stranded wires without end sleeves just a screwdriver will do. 

The terminated wires are easy to release with a screwdriver. 

 

 

Technical Data 

 

Inputvoltage 

0 … 10 V DC 

Outputvoltage 

0 … 10 V DC 

 

Input 

operating voltage U

N

 

24 V AC/DC 

current consumption 

  at 24 V AC 

max. 30 mA 

  at 24 V DC 

19 mA 

current consumption (input YR) 

  at 10 V DC 

max. 2 mA 

operating voltage range 

0.85 ... 1.2 × U

duty cycle 

100 % 

status indication of the output 

red LED, intensity of the LED is proportional to the 

manipulated variable 

switching AUTO/ON 

proof against short-circuits 

 

Breaking Capacity of Switch 

breaking capacity max. 

24 V / 50 mA AC/DC 

breaking capacity min. 

20 mV / 1 

μ

A AC 

mechanical endurance 

5 × 10² switching cycles 

test voltage 

500 V, 50 Hz, 1 min. 

 

Output 

output current (output Y)

 

 

in switch positions 

“AUTO/ON/OFF” 

10 mA 

 

Temperature range 

operating temperature range 

-20 °C ... +55 °C 

storage temperature range 

-25 °C ... +70 °C 

 

Housing 

type of protection (EN 60 529) 

IP20 

material 

polyamide 6.6 V0 

wire cross section 

  single wire 

0.08 - 2.5 mm² 

  stranded wire w/o end sleeve  0.08 - 2.5 mm² 

  stranded wire with end sleeve  0.08 - 1.5 mm² 

dimensions W × H × L 

11.2 × 88 × 60 mm 

weight 

43 g 

mounting position 

any 

mounting  

Standard rail TH35 per IEC 60715

 

 

 

Mounting 

 

On standard rail TH35 per IEC 60715 (35 

×

 7.5 mm),  in junction boxes 

And/or distribution panels. 

 

 

 

 

 

 

 

 

 

 

Installation 

Electric installation and device termination shall be done by qualified persons only, 

by respecting the VDE specifications and local regulations. 

 

1. Power down the equipment. 

 

 

 

 

 

 

 

 

 

 

 

2. Strip the wire by 10 mm. Wire cross section: 

  Solid wire 

0.08 – 2.5 mm² 

  Stranded wire w/o end sleeve  0.08 – 2.5 mm² 

  Stranded wire with end sleeve  0.08 – 1.5 mm² 
a) Solid wires and wire with end sleeves are plugged directly 

  Insert the wire straight into the contact and press until the wire snaps 

  In the spring. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

b) When terminating stranded wires without end sleeves it is necessary 

  to open the spring with a flat-bladed screwdriver (blade width max. 

  3.0 mm): enter the screwdriver to the test sleeve situated below the 

  Contact and remove the screwdriver. 

 
3. Device connection per wiring diagram. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
4. Release a wire 

Open the spring by inserting a flat-bladed screwdriver 

(blade width max. 3.0 mm) to the test sleeve situated 

below the conact and remove the wire. 

 

 

 

 

 

 

5. Release the Module from the standard rail 

Slightliy push the clamp at the bottom  of the module with a flat-bladed screwdriver and 

draw off upwards. 

 

 

Connecting Bridge 

The connecting bridge (Order-Nr. PCD7.L291) allows to interconnect up to 10 coupling 

modules (total currenct max. 2 A). 

 

 

 

 

 

 

 

 

 

 

 

 

Cut the needed number of contacts with wire cutting pliers at the respective predetermined 

cutting point. Then insert the connecting bridge from the top into the contact slot and press 

it downwards into place. 

 

 

 

 

 

 

 

 

 

 

 

 

 

The tails of the connecting bridge carry potential, therefore 

place the bridge in the middle of the aligned modules to 

eliminate any accidential touch. 

 

 

 

 

 

Wiring 

Wiring diagram 