ardware manual for PCD3 series │ Document 26-789 ENG19│ 2018-06-29
Internal power of the PCD3.T76x head stations
RIO (Remote Input Output) head stations
4-3
4
4.2
Internal power of the PCD3.T76x head stations
GND
+5V
CLR
0V
+V
(16...24V)
LED
24V
39V
PTC
PCD3
+24 V
Voltage-
monitor
5V
PCD-Bus
S
up
pl
y
24
V
D
C
DC
DC
DC
DC
The PCD3.T76x head stations provide the following internal supply currents for the
plugged or connected modules:
Type
+5V
V+
The load capacity of the + V bus depends on the load of
the 5 V bus as follows (the more accurate the 24 VDC, the
higher the possible load):
PCD3.T76x
650 mA
- 10%
: 275 -
I
5 V Bus
[mA]
+10%
4
- 20%
: 150 -
I
5 V Bus
[mA]
+25%
15
- 25%
: 100 [mA]
+30%
24 V
24 V
24 V
When planning PCD3 systems, it must be checked whether the two internal power
supplies are not overloaded. This control is particularly important when using
analog, counting and positioning modules, as these sometimes have a fairly large
power consumption.
It is recommended to use the PG5 device configurator.