Hardware manual PCD1.M2220-C15 │ Document 27-640 – Version ENG03 │ 2020-03-25
Saia-Burgess Controls AG
Firmware
CPU/processor unit
3-4
3
3.4
Firmware (COSinus update)
The firmware of the PCD1 is saved in a flash memory. A firmware update can be
downloaded at any time to the PCD1 using the Saia PG5
®
.
To do this, proceed as follows:
and download the latest firmware version
●
Establish a connection between the Saia PG5
®
and the CPU in the same way
as downloading an application (according to the available equipment, serial with
PGU cable, modem, USB, Ethernet)
A modem connection is never reliable. Modems can block a signal so
that remote access is no longer possible. In these cases, a visit to the
system is required. Other connection options are preferable.
● Open the “Online Configurator” and go online
● In the Tools menu, select “Update Firmware” and select the path for the file of
the new firmware version with the Search function. Make sure that only one file
is selected for the download
●
Start the download