87
Setting range 0.0s
~
3600.0s
It is used to set the delay time for the inverter to change the terminal state when the MI terminal changes.
Currently, only MI1, MI2, and MI3 have the function of setting the delay time.
04-38
MI terminal valid mode selection 1
Factory setting
0
Setting range
0
High level valid
1
Low level valid
Single digit
MI1
Tens digital
MI2
Hundreds digital
MI3
Thousands digital
MI4
Ten thousands
digital
MI5
Used to set the active status mode of the digital input terminal. When the selection is active high, the
corresponding MI terminal is valid when connected to the DCM, and the disconnection is invalid. When the
selection is active low, the corresponding MI terminal is invalid when it is connected to the DCM, and the
disconnection is valid.
05 Multi-Speed, Simple PLC Control
The S3100A's multi-speed command is more abundant than the normal multi-speed. In addition to the
multi-speed function, it can also be used as a voltage source for V/f separation and a given source of process PID.
For this reason, the dimension of the multi-speed command is a relative value.
05-00
Multi-step speed command 0
Factory setting
0.0%
05-01
Multi-step speed command 1
Factory setting
0.0%
05-02
Multi-step speed command 2
Factory setting
0.0%
05-03
Multi-step speed command 3
Factory setting
0.0%
05-04
Multi-step speed command 4
Factory setting
0.0%
05-05
Multi-step speed command 5
Factory setting
0.0%
05-06
Multi-step speed command 6
Factory setting
0.0%
05-07
Multi-step speed command 7
Factory setting
0.0%
05-08
Multi-step speed command 8
Factory setting
0.0%
05-09
Multi-step speed command 9
Factory setting
0.0%
05-10
Multi-step speed command 10
Factory setting
0.0%
05-11
Multi-step speed command 11
Factory setting
0.0%
05-12
Multi-step speed command 12
Factory setting
0.0%
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...