60
5 DESCRIPTION OF FUNCTIONAL PARAMETERS
This chapter will give a detailed description of all functional parameters. It is divided into various parameter
groups according to the attributes of the parameters; making parameter setting easier. In most applications, users
can complete the settings before operation according to the related parameter settings in the parameter group.
The parameter groups are as follows
Parameter Function
Parameter Function
Parameter Function
00
Basic function
parameters
06
Output terminal
parameters
12
Serial communication
parameters
01
Motor control
parameters
07
Start and stop control
parameters
13
Wobble frequency
counting parameters
02
Vector control
parameters
08
Man-machine
interface parameters
17
Torque control
parameters
03
V/f control
parameters
09
Accessibility
parameters
22
Control optimization
parameters
04
Input terminal
parameters
10
PID control
parameters
99
Monitoring parameters
05
Multi-speed, simple
PLC control
11
Fault and protection
parameters
Indicates that the parameters can be set during operation
00 Basic Functions Parameters
00-00
Command source selection
Factory setting
0
Setting range
0
Keyboard command (LED off)
1
Terminal command (LED on)
2
Communication command (LED flicker)
Select the input channel for inverter control commands.
Inverter control commands include: start, stop, forward, reverse, and jog.
0:
Keyboard command channel ("LOC/REM" indicator off)
Run command control is performed by the RUN, STOP/RESET buttons on the operation panel.
1: Terminal command channel ("LOC/REM" indicator on)
Run command control is performed by multi-function input terminals FWD, REV, FJOG, RJOG, etc.
2: Communication command channel ("LOC/REM" indicator
flicker)
The running command is given by the host computer through communication.
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...