137
ON signal, and then the counter stops counting.
When the count value reaches the designated count value 13-09, the multi-function output terminal (Function 9)
outputs an ON signal. At this time, the counter continues to count until the "set count value" stops the counter.
The designated count value 13-09 should not be greater than the set count value 13-08.
Figure 5-30 is a schematic diagram of the set count value arrival and designated count value arrival functions.
Designated count value
relay
Set count value
MO1
Count pulses
MI5
1
9
8
7
6
2
5
4
3
Figure 5-30 Schematic diagram of set count value and designated count value
17 Torque Control Parameters
17-00
Speed/torque control method selection
Factory setting
0
Setting range
0
Speed control
1
Torque control
Select the control method of the inverter.
The S3100A's multi-function input M I terminal has two functions related to torque control: torque control
prohibition (function 29) and speed control/torque control switching (function 46). These two terminals should be
used in conjunction with 17-00 to achieve the switching between speed and torque control.
When the speed control/torque control switching terminal is invalid, the control mode is determined by 17-00. If
the speed control/torque control switching is effective, the control mode is equivalent to the reverse of the value of
17-00.
When the torque control inhibit terminal is valid, the inverter is fixed to speed control mode.
17-01
Torque setting source selection in torque control mode
Factory setting
0
Setting range
0
Digital setting(17-03)
1
AVI1
2
AVI2/ACI
3
Reserved
4
PULSE
5
Communication setting
6
MIN(AVI1, AVI2/ACI)
7
MAX(AVI1, AVI2/ACI)
1-7 option full scale, corresponding to 17-03 digital setting
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...