96
06-22
MO
output terminal valid state selection
Factory setting
0
Setting range
0
Positive logic
1
Negative logic
Single digit
MO1
Tens digital
Relay RA-RB-RC
Hundreds digital
Reserved
Thousands digital
Reserved
Ten thousands
digital
DFM(M)
Define the output logic of output terminals MO1, relays RA-RB-RC and DFM(M).
0: positive logic, the digital output terminal and the corresponding common terminal are connected to the valid
state, and disconnected to the invalid state;
1: Inverse logic, the digital output terminal and the corresponding common terminal are connected to the invalid
state, and disconnected to the valid state.
07 Start and Stop Control Parameters
07-00
Startup mode
Factory setting
0
Setting range
0
Direct start
1
Rotation speed tracking restart
2
Pre-excitation start
3
Reserved
0: Direct start:
If the startup DC braking time is set to 0, the inverter starts to run from the startup frequency. If the startup DC
braking time is not 0, then DC braking first, and then start running from the startup frequency. Applicable to small
inertial loads,where the motor may rotate when starting.
1: Rotation speed tracking restart:
The inverter first judges the speed and direction of the motor, and then starts at the tracked motor frequency, and
implements the smoothing of the rotating motor.
Start without sliding. It is suitable for restart after instantaneous power failure of large inertia load. In order to
ensure the performance of speed tracking and restart, it is necessary to set the motor 01 group parameters
accurately.
2: Pre-excitation start:
Used to establish the magnetic field before the motor runs. For the pre-excitation current and time, please refer to
the description of parameters 07-03 and 07-04.
If the pre-excitation time is set to 0, the inverter cancels the pre-excitation process and starts from the startup
frequency. If the pre-excitation time is not 0, pre-excitation first and then start, can improve the dynamic response
performance of the motor.
Содержание S3100A Series
Страница 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Страница 23: ...19 Size 3 Unit mm S3100A 2T5 5G 2T7 5G S3100A 4T7 5G 11P 4T18 5G 22P Size 4 Unit mm S3100A 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...