8 Communication Parameters
08-00
Communication address
Factory setting
1
Setting range 0
~
254
If the system is set to RS485 series communication interface control or monitoring, each drive shall set its
individual address in this parameter. And each address in a same connection net shall be ONLY, shall not be
repeated.
08-01
Communication transmitting speed
Factory setting
9.6
Setting range 4.8
~
115.2 kbits/s
A personal computer may be connected to the AC drive via its RS485 serial port. The PC may then be used to set
or modify the internal parameters of the AC drive, or to control and monitor the AC drive operation. and operation
status of the motor drive shall also be monitored by this parameter. This parameter is to set communication
transmission speed.
08-02
Transmitting fault treatment
Factory setting
3
Setting range
0:Warning and running continuously
1:Warning and deceleration to stop
2:Warning and coasting to a stop
3:No warning and running continuously
A personal computer may be connected to the AC drive via its RS485 serial port. The PC may then be used to set
or modify the internal parameters of the AC drive, or to control and monitor the AC drive operation. and operation
status of the motor drive shall also be monitored by this parameter. This parameter is to set communication
transmission speed.
08-03
Time out detected
Factory setting
0
Setting range
0 :Not detected
1
~
100 s
This parameter is used to set the communication and Keypad transmission timeout time.
08-04
Communication Material Format
Factory setting
0
Setting range
0:7,N,1 FOR ASCII 1:7,N,2 FOR ASCII
2:7,E,1 FOR ASCII 3:7,O,1 FOR ASCII
4:7,E,2 FOR ASCII 5:7,O,2 FOR ASCII
6:8,N,1 FOR ASCII 7:8,N,2 FOR ASCII
8:8,E,1 FOR ASCII 9:8,O,1 FOR ASCII
10:8,E,2 FOR ASCII 11:8,O,2 FOR ASCII
12:8,N,1 FOR RTU 13:8,N,2 FOR RTU
14:8,E,1 FOR RTU 15:8,O,1 FOR RTU
16:8,E,2 FOR RTU 17:8,O,2 FOR RTU
Computer Link:For RS485 series communication interface, each S200 shall be prepared with individual
communication address in Parameter 8-00, thus inverter shall control it based on the individual communication
addresses..